| Plan Review Notes For Permit 01051470 |
| Permit Number |
01051470 |
|
| Review Stop |
R |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2002-05-20 00:00:00 | TRUSS DRAWINGS CHECKLIST: | | | 1-TRUSS ENGINEER TO SIGN, SEAL AND DATE | | | TRUSS PLAN AS REQUIRED BY CHAPTER 471 | | | FLORIDA STATUTES. | | | 2-TRUSS ENGINEER TO PROVIDE ORIGINAL | | | SIGNATURE, SEAL AND DATE ON ALL | | | ENGINEERED DRAWINGS & MICROLLAM BEAMS | | | AS REQUIRED BY CHAPTER 471 FL STATUTES | | | 3-MICROLLAM BEAMS ENGINEERED BEAMS ARE | | | NOT LEGIBLE. ALSO, WHAT'S THE DESIGN | | | CRITERIA USED. ASCE 7-98 140MPH AS THE | | | ENGINEERED TRUSSES? | | | 4-ENGINEER OF RECORD TO REVISE TRUSS | | | ANCHOR SCHEDULE TO RESIST THE UPLIFT | | | LOADS AS CALCULATED ON THE ENGINEERED | | | TRUSSES. SEE ENGINEERED TRUSSES. |
|