| Plan Review Notes For Permit 01051470 |
| Permit Number |
01051470 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2003-01-07 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE RISER DIAGRAM AND | | | PANEL SCHEDULE NEED TO CORRELATE. | | | PLEASE SHOW SIZES OF PANELS AND MATCH | | | UP WITH RISER.("D"). | | | | | | 2)NOTE: PLEASE SEE PANEL SCHEDULES AND | | | CORRELATE WIRE/PANELS/OCP. NOTE 200A | | | BRKR ON #3AWG. PLEASE ALSO SEE SOME | | | OTHER WIRE SIZES TOO SMALL FOR OCP. | | | | | | 3)NOTE: PLEASE NOTE AHU #1 SHOWN W/ #8 | | | AWG. PLEASE NOTE WIRE IS SIZED PER KW | | | OF UNIT AND NOT PER 65% DERATING.424-3 | | | SHOWN AS #6 ON PANEL SCHEDULE. | | | 4)NOTE: PLEASE NOTE PANEL "F" FEEDS "G" | | | AND LOAD EXCEEDS 80% RATING OF BRKR?/ | | | PLEASE ADJUST. | | | | | | 5)NOTE: PLEASE SEE LOAD FOR RANGE AND | | | CLARIFY LOAD AT 3KW? | | | | | | PLEASE GO OVER PLANS AND SUBMIT THE | | | ABOVE INFOMRATION FOR REVIEW. IF THERE | | | ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | 6)NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI | | | PROTECTED. 210-8-A-6 |
|