| Plan Review Notes For Permit 01051470 |
| Permit Number |
01051470 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-09-15 00:00:00 | APPROVED WITH PROVISO: | | | | | | 1-ENTRY DOORS WITH SIDELITES, FRENCH | | | DOORS WITH SIDELITES AND BAY WINDOWS | | | CALL FOR 2X STRUCTURAL MULLIONS. | | | PROVIDE COMPLETE SPECIFICATIONS AND | | | CONNECTION DETAILS SHOWING THE SUPPORT | | | TO STRUCTURE AND TO WINDOWS/DOORS. | | | -ALSO, CLARIFY WHAT ASSEMBLIES ARE | | | GOING TO USE THE STRUCTURAL MULLIONS | | | SUBMITTED IN THE PRODUCT APPROVAL. | | | 2-ENGINEER OF RECORD TO REVIEW ALL | | | WINDOW, DOORS, MULLIONS PRODUCT | | | APPROVALS TO ASSURE THAT THEY MEET THE | | | DESIGN PRESSURES HE CALCULATED. (USE | | | SHOP DRAWINGS REVIEW STAMP). | | | 3-PROVIDE PRODUCT APPROVAL FOR: | | | -ENTRY DOORS WITH SIDELITES ASSEMBLY. | | | -INSWING FRENCH DOORS. SEE PLANS. | | | -EXTERIOR SWING DOORS. SEE PLANS. | | | -UL LISTING FOR BBQ. | | | -PROVIDE UL LISTING FOR FIREPLACE AND | | | SUBMITT TWO COPIES. | | | 4-BORING TEST REPORT SHALL BE DONE | | | USING SECTION 1804.2.7 OF CITY | | | AMENDMENTS TO SBC 1997, NOT SOUTH | | | FLORIDA BUILDING CODE. | | | -PROVIDE TWO COPIES. |
|