| 2001-09-18 00:00:00 | *********** REVISION REQUESTED ********* |
| | |
| | PLEASE NOTE THAT NOT ALL ITEMS WERE |
| | CHANGED ON THE PLANS BY ARCHITECT OF |
| | RECORD. PLEASE NOTE MANY ITEMS WERE |
| | REDLINED ON PLANS. THESE WERE COMMENTS |
| | FROM FIRST TWO REVIEWS. |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | NOW THAT TWO MAIN DISCONNECTS ARE BEING |
| | INSTALLED TO MEET GROUPING OF MAINS PER |
| | 230-72. PLEASE SUBMIT AIC RATINGS FOR |
| | MAINS. |
| | |
| | 2)NOTE: PLEASE NOTE THAT RISER DIAGRAM |
| | NEEDS TO BE REVISED TO INCLUDE NEW MAIN |
| | DISCONNECTS AND WIRING. |
| | |
| | 3)NOTE: PLEASE NOTE MISSING EQUIPMENT |
| | GROUNING CONDUCTORS PER 250-122 BETWEEN |
| | MAIN AND PANELS. |
| | |
| | 4)NOTE: PLEASE NOTE THAT PANELS NOW ONLY |
| | NEED TO BE SHOWN AS "MLO". |
| | |
| | 5) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 6) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | |
| | 7) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL. |
| | PER 250-50. |
| | |
| | 8)NOTE: PLEASE NOTE MISSING OUTLETS AND |
| | LTS REQ`D FOR AHU`S AND OUTLETS FOR |
| | COND UNITS. 210-8/210-63/210-70/309.1 |
| | |
| | PLEASE SUBMIT THE ABOVE AS A REVISION |
| | FOR REVIEW, BEFORE ANY ROUGH ELECTRICAL |
| | INSPECTION IS CALLED IN. PLEASE ALSO |
| | NOTE THAT THERE WILL BE A FEE DUE FOR |
| | REVISION. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |