Plan Review Notes
Plan Review Notes For Permit 01051470
Permit Number 01051470
Review Stop E
Sequence Number 3
Notes
Date Text
2001-09-18 00:00:00*********** REVISION REQUESTED *********
  
 PLEASE NOTE THAT NOT ALL ITEMS WERE
 CHANGED ON THE PLANS BY ARCHITECT OF
 RECORD. PLEASE NOTE MANY ITEMS WERE
 REDLINED ON PLANS. THESE WERE COMMENTS
 FROM FIRST TWO REVIEWS.
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 NOW THAT TWO MAIN DISCONNECTS ARE BEING
 INSTALLED TO MEET GROUPING OF MAINS PER
 230-72. PLEASE SUBMIT AIC RATINGS FOR
 MAINS.
  
 2)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 NEEDS TO BE REVISED TO INCLUDE NEW MAIN
 DISCONNECTS AND WIRING.
  
 3)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNING CONDUCTORS PER 250-122 BETWEEN
 MAIN AND PANELS.
  
 4)NOTE: PLEASE NOTE THAT PANELS NOW ONLY
 NEED TO BE SHOWN AS "MLO".
  
 5) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 6) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 7) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL.
 PER 250-50.
  
 8)NOTE: PLEASE NOTE MISSING OUTLETS AND
 LTS REQ`D FOR AHU`S AND OUTLETS FOR
 COND UNITS. 210-8/210-63/210-70/309.1
  
 PLEASE SUBMIT THE ABOVE AS A REVISION
 FOR REVIEW, BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. PLEASE ALSO
 NOTE THAT THERE WILL BE A FEE DUE FOR
 REVISION. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372