2001-08-29 00:00:00***************** UNSAT ****************
  
 PLEASE SEE THE FOLLOW NOTES, NOT ALL
 NOTES WERE ADRESSED FROM FIRST REVIEW.
  
 1)NOTE: PLEASE NOTE THAT ONE LINE DIA-
 -GRAM SHOWS TWO PANELS, ONE LH AND ONE
 RH. PLEASE CLARIFY LOCATIONS OF PANELS.
 MAINS NEED TO BE GROUPED PER 230-72.
 PLANS SHOW ONLY ONE PANEL IN GARAGE?
 WHERE IS THE OTHER PANEL?
  
 2)NOTE: PLEASE NOTE ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE ARE TO BE SHOWN AS
 GFI/GFI PROTECTED PER 210-8-A-6.
 PLEASE NOTE THAT OUTLET SPACING NEEDS TO
 MEET 210-52-C-1. WITHIN 2' OF COUNTER
 END AND EVRY 4' THER-AFTER.
  
 3)NOTE: PLEASE NOTE MISSING REQ`D LIGHT
 AND RECEPT FOR ALL AHU`S IN ATTIC SPACES
 PER 210-70 AND 210-63.
 PLEASE ALSO NOTE MISSING OUTLET FOR
 COND UNITS PER 309-1 OF THE MECH CODE.
  
 4)NOTE: PLEASE NOTE MISSING SOME OUTLETS
 PER 210-52 UPSTAIRS.
  
 5)NOTE: PLEASE NOTE THAT BLDG/FOOTER
 STEEL IS REQ`D PER 250-50 FOR GROUNDING
 ELECTRODE SYSTEM.
  
 PLEASE NOTE THAT SOME OF THE ITEMS ABOVE
 COULD HAVE BEEN REDLINED ON PLANS BUT
 MAIN SERVICE PANEL LOCATION ON PLANS
 MUST BE GROUPED, GROUNDING ELECTRODE
 TO BLDG. STEEL.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  