| 2001-08-29 00:00:00 | ***************** UNSAT **************** |
| | |
| | PLEASE SEE THE FOLLOW NOTES, NOT ALL |
| | NOTES WERE ADRESSED FROM FIRST REVIEW. |
| | |
| | 1)NOTE: PLEASE NOTE THAT ONE LINE DIA- |
| | -GRAM SHOWS TWO PANELS, ONE LH AND ONE |
| | RH. PLEASE CLARIFY LOCATIONS OF PANELS. |
| | MAINS NEED TO BE GROUPED PER 230-72. |
| | PLANS SHOW ONLY ONE PANEL IN GARAGE? |
| | WHERE IS THE OTHER PANEL? |
| | |
| | 2)NOTE: PLEASE NOTE ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE ARE TO BE SHOWN AS |
| | GFI/GFI PROTECTED PER 210-8-A-6. |
| | PLEASE NOTE THAT OUTLET SPACING NEEDS TO |
| | MEET 210-52-C-1. WITHIN 2' OF COUNTER |
| | END AND EVRY 4' THER-AFTER. |
| | |
| | 3)NOTE: PLEASE NOTE MISSING REQ`D LIGHT |
| | AND RECEPT FOR ALL AHU`S IN ATTIC SPACES |
| | PER 210-70 AND 210-63. |
| | PLEASE ALSO NOTE MISSING OUTLET FOR |
| | COND UNITS PER 309-1 OF THE MECH CODE. |
| | |
| | 4)NOTE: PLEASE NOTE MISSING SOME OUTLETS |
| | PER 210-52 UPSTAIRS. |
| | |
| | 5)NOTE: PLEASE NOTE THAT BLDG/FOOTER |
| | STEEL IS REQ`D PER 250-50 FOR GROUNDING |
| | ELECTRODE SYSTEM. |
| | |
| | PLEASE NOTE THAT SOME OF THE ITEMS ABOVE |
| | COULD HAVE BEEN REDLINED ON PLANS BUT |
| | MAIN SERVICE PANEL LOCATION ON PLANS |
| | MUST BE GROUPED, GROUNDING ELECTRODE |
| | TO BLDG. STEEL. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |