2001-06-02 00:00:00REVIEW NOTES:FAILED
  
 1) PAGE A-10 SEC. 15400 PLUMBING NOTES.
 PROVIDE MANUFACTURE SPECIFICATIONS FOR
 LEAD WRAP PIPE SOUND INFORMATION.
  
 2) SANITARY RISER DIAGRAM DOES NOT
 COMPLY WITH SPC-94. SUBMIT RISER DIAGRAM
 THAT MEETS CODE REQUIREMENTS AND
 REFLECTS FLOOR LAYOUT AS IT WILL BE IN-
 STALLED.
  
 REVIEW BY KEN STEVENS. ANY QUESTIONS
 CALL (561) 659-8096 EXT. 8377