Plan Review Notes
Plan Review Notes For Permit 01051470
Permit Number 01051470
Review Stop E
Sequence Number 1
Notes
Date Text
2001-06-12 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT ALL PLANS THAT
 ARE SIGNED AND SEALED ARE TO HAVE A
 TITLE BLOCK 61G15-23.002 .ALSO PLANS
 ARE TO BE DATED PER 481.221 AND 471.025
 WHEN SIGNED AND SEALED.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 4) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
  
 5)NOTE: PLEASE NOTE THAT GARAGE OUTLETS
 NEED TO BE SHOWN AS GFI/GFI PROTECTED
 PER 210-8
 ALSO OUTSIDE OUTLETS.
  
 6) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
 MISSING OUTLET IN FRONT
  
 7)NOTE: PLEASE NOTE ALL A/C EQUIPMENT
 NOT SHOWN ON PLANS.
 MISSING DISCONNECTS PER 440-11
 PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 8) NOTE: PLEASE SHOW ALL OUTLETS
 SERVINGKITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
  
 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 10)NOTE: PLEASE NOTE THAT PLANS DO NOT
 SHOW LOCATIONS PF PANELS? PLEASE NOTE
 GROUPING OF MAINS PER 230-72
  
 11)NOTE: PLEASE SHOW GROUNDING
 ELECTRODEGOING TO BUILDING STEEL AND
 COLD WATER
 PER 250-50.
  
 12)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 FOR BOTH PANELS. THIS MAY CHANGE IN THE
 COARSE OF BLDG BUT IS REQ`D FOR
 PRELIMINARY CIRCUITING. 215-5
  
 13)NOTE: PLEASE NOTE THAT LOAD
 CALCULATIONS SHOW ALL AHU HEAT LOADS
 BEING DERATED AT 40%. PLEASE CLARIFY.
 ALL LOAD CALCSARE TO BE DONE IN ACCORD
 TO NEC AND ART 220. PLEASE NOTE THAT
 THE MAX DEDUCTION FOR DERATING AHU`S
 AND HEAT STRIP LOADS IS 65%. PLEASE SEE
 ART 220.
  
 14)NOTE: PLEASE NOTE THAT SUB PANEL FOR
 DOCK WAS NOT SHOWN ON RISER DIAGRAM??
 PLEASE SHOW ON LINE DIAGRAM. BEING SUB-
 -PANEL FROM PANEL ?? SHOW ON PANEL
 SCHEDULE.
 CONDUIT SIZES/WIRE SIZES ETC.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372