| 2001-06-12 00:00:00 | ******************* UNSAT ************* |
| | |
| | 1)NOTE: PLEASE NOTE THAT ALL PLANS THAT |
| | ARE SIGNED AND SEALED ARE TO HAVE A |
| | TITLE BLOCK 61G15-23.002 .ALSO PLANS |
| | ARE TO BE DATED PER 481.221 AND 471.025 |
| | WHEN SIGNED AND SEALED. |
| | |
| | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 3) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 4) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | |
| | |
| | 5)NOTE: PLEASE NOTE THAT GARAGE OUTLETS |
| | NEED TO BE SHOWN AS GFI/GFI PROTECTED |
| | PER 210-8 |
| | ALSO OUTSIDE OUTLETS. |
| | |
| | 6) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| | BY 210-52E OF THE NEC. |
| | MISSING OUTLET IN FRONT |
| | |
| | 7)NOTE: PLEASE NOTE ALL A/C EQUIPMENT |
| | NOT SHOWN ON PLANS. |
| | MISSING DISCONNECTS PER 440-11 |
| | PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| | MECHANICAL CODE. |
| | |
| | 8) NOTE: PLEASE SHOW ALL OUTLETS |
| | SERVINGKITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECT--ED PER 210-8-A-6. |
| | |
| | 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 10)NOTE: PLEASE NOTE THAT PLANS DO NOT |
| | SHOW LOCATIONS PF PANELS? PLEASE NOTE |
| | GROUPING OF MAINS PER 230-72 |
| | |
| | 11)NOTE: PLEASE SHOW GROUNDING |
| | ELECTRODEGOING TO BUILDING STEEL AND |
| | COLD WATER |
| | PER 250-50. |
| | |
| | 12)NOTE: PLEASE SUBMIT PANEL SCHEDULES |
| | FOR BOTH PANELS. THIS MAY CHANGE IN THE |
| | COARSE OF BLDG BUT IS REQ`D FOR |
| | PRELIMINARY CIRCUITING. 215-5 |
| | |
| | 13)NOTE: PLEASE NOTE THAT LOAD |
| | CALCULATIONS SHOW ALL AHU HEAT LOADS |
| | BEING DERATED AT 40%. PLEASE CLARIFY. |
| | ALL LOAD CALCSARE TO BE DONE IN ACCORD |
| | TO NEC AND ART 220. PLEASE NOTE THAT |
| | THE MAX DEDUCTION FOR DERATING AHU`S |
| | AND HEAT STRIP LOADS IS 65%. PLEASE SEE |
| | ART 220. |
| | |
| | 14)NOTE: PLEASE NOTE THAT SUB PANEL FOR |
| | DOCK WAS NOT SHOWN ON RISER DIAGRAM?? |
| | PLEASE SHOW ON LINE DIAGRAM. BEING SUB- |
| | -PANEL FROM PANEL ?? SHOW ON PANEL |
| | SCHEDULE. |
| | CONDUIT SIZES/WIRE SIZES ETC. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |