2001-06-06 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATING WAS SHOWN
 FOR PANELS , BUT NOT FOR MAINS. PER
 110-9-AND 215-5
  
 2) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING FAMILY ROOM.
  
 3) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
 FRONT RECEPT.
  
 4) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
 MISSING OUTSIDE AND IN ATTIC FOR AHU IN
 GARAGE.
  
 5)NOTE: PLEASE NOTE OUTLET FOR KITCHEN
 PENINSULAR PER 210-52-C-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  