| Plan Review Notes For Permit 01051434 |
| Permit Number |
01051434 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-06 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE:PLEASE SEE 210-52-C-3 FOR MISSING | | | OUTLET AT PENINSULAR IN KITCHEN. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | AIC RATINGS HAVE BEEN SUBMITTED FOR | | | PANELS BUT NOT FOR MAINS? | | | | | | 3) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | MISSING IN FAMILY ROOM. | | | | | | 4) PLEASE NOTE MISSING OUTLET(S) REQ`D | | | BY 210-52E OF THE NEC. | | | FRONT RECEPT. | | | | | | | | | 5) PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | | MECHANICAL CODE. | | | OUTSIDE AND IN ATTIC IN GARAGE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|