| Plan Review Notes For Permit 01051400 |
| Permit Number |
01051400 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-12-05 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASENOTE THAT LOCATION OF | | | POOL PANEL IS NOT SHOWN ON PLANS. | | | GROUPING OF MAINS? 230-72 PLEASE NOTE | | | THAT POOL PANEL IS SHOWN ONRISER | | | DIAGRAM COMING FROM METERCAN? PLEASE | | | CLARIFY METER/MAIN COMBO AND WHY ISNT | | | POOL PANEL BEING FED FROM THIS METER/MAI | | | N LIKE A/C UNIT? PLEASE CLARIFY | | | | | | 2)NOTE: PLEASE NOTE THAT PLANS AND | | | PANEL SCHEDULES SHOWN METER/MAIN AND | | | RSIER DIAGRAM IS NOT CLEAR ON THIS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|