Plan Review Notes
Plan Review Notes For Permit 01051400
Permit Number 01051400
Review Stop E
Sequence Number 3
Notes
Date Text
2001-12-05 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASENOTE THAT LOCATION OF
 POOL PANEL IS NOT SHOWN ON PLANS.
 GROUPING OF MAINS? 230-72 PLEASE NOTE
 THAT POOL PANEL IS SHOWN ONRISER
 DIAGRAM COMING FROM METERCAN? PLEASE
 CLARIFY METER/MAIN COMBO AND WHY ISNT
 POOL PANEL BEING FED FROM THIS METER/MAI
 N LIKE A/C UNIT? PLEASE CLARIFY
  
 2)NOTE: PLEASE NOTE THAT PLANS AND
 PANEL SCHEDULES SHOWN METER/MAIN AND
 RSIER DIAGRAM IS NOT CLEAR ON THIS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  