| Plan Review Notes For Permit 01051399 |
| Permit Number |
01051399 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-02 00:00:00 | *************BUILDING UNSAT************* | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) ON SHEET 3A, DETAIL A3 IS MISLABELED | | | AS A4. PLEASE CORRECT. | | | | | | 3) PROVIDE CONNECTION DETAILS FOR GIRDER | | | FG1 AT THE COLUMNS ON SHEET 3A. | | | | | | 4) INDICATE THE CONNECTORS FOR GIRDERS | | | HGT AND T8. | | | | | | 5) ON SHEET 4A THE RIGHT ELEVATION IS | | | MISTAKENLY LABELED AS LEFT ELEVATION. | | | PLEASE CORRECT. | | | | | | 6) PROVIDE MANUAL J CALCULATIONS AS | | | REQUIRED BY 1997 FLORIDA ENERGY | | | EFFICIENCY CODE. | | | | | | 7) THE TIE BEAM ELEVATION OF 15'-0" AT | | | THE BOTTOM OF SHEET 4A IS INCORRECT. IT | | | SHOULD BE 12'-0". PLEASE CORRECT. | | | | | | | | | TRUSSES | | | UNSAT | | | | | | 1) THE MEAN ROOF HEIGHTS GIVEN ON THE | | | TRUSS DRAWINGS ARE INCONSISTENT WITH | | | EACH OTHER AND DO NOT CONCUR WITH THE | | | MEAN ROOF HEIGHT OF THE STRUCTURE. | | | PLEASE CORRECT. | | | | | | 2) THE TRUSS DRAWINGS INCORRECTLY | | | REFERENCE THE 97 SBCCI,WHICH IS AN | | | ORGANIZATION. THE PROPER REFERENCE WOULD | | | BE THE 97 SBC, WHICH IS THE ACTUAL CODE. | | | PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|