| 2001-06-29 00:00:00 | CHECKLIST: |
| | 1-NEED TO FILE NOTICE OF COMMENCEMENT. |
| | 2-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | BRING STAMPED DRAWINGS AND RECEIPT. |
| | 3-UPDATE GENERAL NOTES. SEE COMMENTS. |
| | 4-ROOF DRAINAGE: |
| | A)FLAT ROOF TO HAVE 1/4" PER FT SLOPE, |
| | NOT 1/8". SEC. 1503.1.2.3 SBC 1997. |
| | B)SPECIFY SIZES OF GUTTERS, SCUPPERS& |
| | RAIN LEADERS. SEC 1517.6. SBC 1997. |
| | C)SPECIFY OVERFLOW SCUPPERS. SECTION |
| | 1517.6.4.3 SBC 1997. |
| | 5-REVISE CALCULATED AREAS ON SHEET A-1. |
| | SEE DEFINITION FOR BUILDING AREA. |
| | -SPECIFY HOW MUCH A/C AREA AND NON A/C |
| | AREAS LIKE PORCHES. |
| | 6-SPECIFY SAFETY GLASS WHERE REQUIRED BY |
| | SEC 2405.2 SBC 1997. SEE PLANS. |
| | 7-BEDROOM EGRESS WINDOWS DON'T COMPLY W/ |
| | SEC 1005.4 SBC 1997. WINDOWS SPECIFIED |
| | HAVE A MULLION IN THE MIDDLE. |
| | 8-SPECIFY DESIGN PRESSURES CALCULATED AT |
| | ALL EXTERIOR OPENINGS AS REQUIRED BY |
| | SECTION 1606 SBC 1997. |
| | 9-"WIDTH OF STAIRS SHALL NOT DECREASE IN |
| | THE DIRECTION OF EXIT TRAVEL". SECTION |
| | 1007.6.2 SBC 1997. REVISE AS REQUIRED. |
| | 10-PROVIDE ATTIC ACCESS AT NEW ROOF IF |
| | CLEAR ATTIC SPACE IS MORE THAN 24". |
| | PROVIDE CROSS SECTION SHOWING PROFILE |
| | OF ROOF TRUSSES TO DETERMINE HEIGHT. |
| | SECTION 2309.6 SBC 1997. |
| | 11-ROOF VENTILATION: |
| | A)SPECIFY VENTILATION FOR FLAT ROOF. |
| | B)CLARIFY HOW VENTILATION IS ACHIEVED |
| | THRU THE DRIP EDGE. PROVIDE DETAIL & |
| | SPECS. SECTION 2309.7 SBC 1997. |
| | 12-REVISE THE DESIGN CERTIFICATION FOR |
| | BUILDING CODE COMPLIANCE FORM. THE |
| | MEAN ROOF HEIGHT & VELOCITY PRESSURE |
| | DON'T MATCH. SEE TABLE 1606.2A SBC/97 |
| | -ARCHITECT TO WRITE LICENSE # ON FORM |
| | AS REQUIRED BY CHAPTER 481 FL. ST. |
| | 13-SPECIFY DRAFSTOPPING MATERIAL AND |
| | LOCATION AT SECOND FLOOR FRAMING PLAN. |
| | SEC 2305.2 SBC 1997. |
| | 14-OWNER TO SIGN & DATE ENERGY CALCS. |
| | 15-REVISE WALL SECTIONS AS REQUIRED. SEE |
| | RECOMMENDATIONS ON SOIL TEST REPORT |
| | FOR SLAB ON GRADE CONSTRUCTION. ALSO |
| | SEE SHEET A-4 FOR ADDITIONAL COMMENTS |
| | 16-SOIL TEST REPORT SHOWS ROOTS AND |
| | ORGANIC MATERIALS. REMOVE THEM BEFORE |
| | CONSTRUCTION. SEC 1804.1.8 SBC 1997. |
| | 17-PROVIDE PRODUCT APPROVAL FOR: |
| | A)ENTRY DOORS (MISSING COPIES OF THE |
| | APPROVED DRAWINGS). |
| | NOTE: VERIFY IF APPROVED DRAWINGS |
| | COVER THE DOOR SHOWN ON ARCHITECT'S |
| | EXTERIOR ELEVATION. |
| | B)ROOF HATCH. |
| | 18-SPECIFY THE UPLIFT LOADS CALCULATED |
| | FOR THE NEW STRUCTURE. SEC 1606 SBC/97 |
| | 19-SEE PLANS FOR ADDITIONAL COMMENTS. |
| | AND, PLEASE RETURN REVIEWED SET AFTER |
| | CORRECTIONS/UPDATES ARE DONE TO THE |
| | ORIGINAL DRAWINGS IN ORDER TO EXPEDITE |
| | THE REVIEW PROCESS. |