Plan Review Notes
Plan Review Notes For Permit 01051389
Permit Number 01051389
Review Stop R
Sequence Number 1
Notes
Date Text
2001-06-29 00:00:00CHECKLIST:
 1-NEED TO FILE NOTICE OF COMMENCEMENT.
 2-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 3-UPDATE GENERAL NOTES. SEE COMMENTS.
 4-ROOF DRAINAGE:
 A)FLAT ROOF TO HAVE 1/4" PER FT SLOPE,
 NOT 1/8". SEC. 1503.1.2.3 SBC 1997.
 B)SPECIFY SIZES OF GUTTERS, SCUPPERS&
 RAIN LEADERS. SEC 1517.6. SBC 1997.
 C)SPECIFY OVERFLOW SCUPPERS. SECTION
 1517.6.4.3 SBC 1997.
 5-REVISE CALCULATED AREAS ON SHEET A-1.
 SEE DEFINITION FOR BUILDING AREA.
 -SPECIFY HOW MUCH A/C AREA AND NON A/C
 AREAS LIKE PORCHES.
 6-SPECIFY SAFETY GLASS WHERE REQUIRED BY
 SEC 2405.2 SBC 1997. SEE PLANS.
 7-BEDROOM EGRESS WINDOWS DON'T COMPLY W/
 SEC 1005.4 SBC 1997. WINDOWS SPECIFIED
 HAVE A MULLION IN THE MIDDLE.
 8-SPECIFY DESIGN PRESSURES CALCULATED AT
 ALL EXTERIOR OPENINGS AS REQUIRED BY
 SECTION 1606 SBC 1997.
 9-"WIDTH OF STAIRS SHALL NOT DECREASE IN
 THE DIRECTION OF EXIT TRAVEL". SECTION
 1007.6.2 SBC 1997. REVISE AS REQUIRED.
 10-PROVIDE ATTIC ACCESS AT NEW ROOF IF
 CLEAR ATTIC SPACE IS MORE THAN 24".
 PROVIDE CROSS SECTION SHOWING PROFILE
 OF ROOF TRUSSES TO DETERMINE HEIGHT.
 SECTION 2309.6 SBC 1997.
 11-ROOF VENTILATION:
 A)SPECIFY VENTILATION FOR FLAT ROOF.
 B)CLARIFY HOW VENTILATION IS ACHIEVED
 THRU THE DRIP EDGE. PROVIDE DETAIL &
 SPECS. SECTION 2309.7 SBC 1997.
 12-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. THE
 MEAN ROOF HEIGHT & VELOCITY PRESSURE
 DON'T MATCH. SEE TABLE 1606.2A SBC/97
 -ARCHITECT TO WRITE LICENSE # ON FORM
 AS REQUIRED BY CHAPTER 481 FL. ST.
 13-SPECIFY DRAFSTOPPING MATERIAL AND
 LOCATION AT SECOND FLOOR FRAMING PLAN.
 SEC 2305.2 SBC 1997.
 14-OWNER TO SIGN & DATE ENERGY CALCS.
 15-REVISE WALL SECTIONS AS REQUIRED. SEE
 RECOMMENDATIONS ON SOIL TEST REPORT
 FOR SLAB ON GRADE CONSTRUCTION. ALSO
 SEE SHEET A-4 FOR ADDITIONAL COMMENTS
 16-SOIL TEST REPORT SHOWS ROOTS AND
 ORGANIC MATERIALS. REMOVE THEM BEFORE
 CONSTRUCTION. SEC 1804.1.8 SBC 1997.
 17-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS (MISSING COPIES OF THE
 APPROVED DRAWINGS).
 NOTE: VERIFY IF APPROVED DRAWINGS
 COVER THE DOOR SHOWN ON ARCHITECT'S
 EXTERIOR ELEVATION.
 B)ROOF HATCH.
 18-SPECIFY THE UPLIFT LOADS CALCULATED
 FOR THE NEW STRUCTURE. SEC 1606 SBC/97
 19-SEE PLANS FOR ADDITIONAL COMMENTS.
 AND, PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS/UPDATES ARE DONE TO THE
 ORIGINAL DRAWINGS IN ORDER TO EXPEDITE
 THE REVIEW PROCESS.