| Notes |
| Date |
Text |
| 2001-06-07 00:00:00 | ********************DENIED************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | SIZE OF ALL DUCT AND SIZE OF GRILLS. | | | | | | PROVIDE INFORMATION ON EXISTING AIR | | | DISTRIBUTION FOR AHU-1.PLAN INDICATES | | | AN ADDITIONAL 580 CFM, WILL THE | | | EXISTING UNIT BE ABLE TO PROVIDE THIS? | | | | | | PLEASE PROVIDE SIZE OF BOTH EXHAUST | | | VENTS (KITCHEN & BATHROOMS). | | | | | | LOCATION OF CONDENSER UNITS NEED TO BE | | | REFLECTED ON PLAN. | | | | | | PLEASE INDICATE SIZE AND LOCATION OF | | | CONDENSATE. | | | | | | | | | NOTE:PRIOR TO CONNECTING TO ANY | | | EXISTING DUCTWORK, CALL FOR AN | | | INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|