Plan Review Notes For Permit 01051389
Permit Number 01051389
Review Stop M
Sequence Number 1
Notes
Date Text
2001-06-07 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
 SIZE OF ALL DUCT AND SIZE OF GRILLS.
  
 PROVIDE INFORMATION ON EXISTING AIR
 DISTRIBUTION FOR AHU-1.PLAN INDICATES
 AN ADDITIONAL 580 CFM, WILL THE
 EXISTING UNIT BE ABLE TO PROVIDE THIS?
  
 PLEASE PROVIDE SIZE OF BOTH EXHAUST
 VENTS (KITCHEN & BATHROOMS).
  
 LOCATION OF CONDENSER UNITS NEED TO BE
 REFLECTED ON PLAN.
  
 PLEASE INDICATE SIZE AND LOCATION OF
 CONDENSATE.
  
  
 NOTE:PRIOR TO CONNECTING TO ANY
 EXISTING DUCTWORK, CALL FOR AN
 INSPECTION.
  