2001-06-04 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS THAT WERE SUBMITTED NEED TO
 CORRELATE W/ NEC 220.
 PLEASE NOTE THAT A/C LOADS ARE NOT DED-
 -UCTED WITH LIGHTING LOADS.
 PLEASE GO OVER LOAD CALCUALTIONS AND
 RE-DO. 215-5
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3)NOTE: PLEASE NOTE THAT 1- 1/0 WIRE IS
 GOING TO THE 200A PANEL? PLEASE NOTE THA
 T 1/0 IS NOT RATED FOR 200A. PLEASE
 VERIFY
  
 4)NOTE: PLEASE NOTE MISSING OUTLET PER
 210-52
  
  
 5) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. NEW ADDITION BLDG STEEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372