| Plan Review Notes For Permit 01051389 |
| Permit Number |
01051389 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-04 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE NOTE THAT THE LOAD | | | CALCULATIONS THAT WERE SUBMITTED NEED TO | | | CORRELATE W/ NEC 220. | | | PLEASE NOTE THAT A/C LOADS ARE NOT DED- | | | -UCTED WITH LIGHTING LOADS. | | | PLEASE GO OVER LOAD CALCUALTIONS AND | | | RE-DO. 215-5 | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 3)NOTE: PLEASE NOTE THAT 1- 1/0 WIRE IS | | | GOING TO THE 200A PANEL? PLEASE NOTE THA | | | T 1/0 IS NOT RATED FOR 200A. PLEASE | | | VERIFY | | | | | | 4)NOTE: PLEASE NOTE MISSING OUTLET PER | | | 210-52 | | | | | | | | | 5) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BUILDING STEEL AND COLD WATER | | | PER 250-50. NEW ADDITION BLDG STEEL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|