Plan Review Notes
Plan Review Notes For Permit 01051385
Permit Number 01051385
Review Stop B
Sequence Number 2
Notes
Date Text
2001-06-30 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SHEET C1 SITES 1999 SBC AND 1999 FL
 ENERGY CODE, THE CITY OF WPB HAS ADOPTED
 THE 1997 SBC AND THE 1997 FLORIDA ENERGY
 CODE. PLEASE CORRECT.
  
 4) ONE SET OF THE ENERGY CALCULATION
 FORMS SUBMITTED WAS NOT SIGNED BY THE
 OWNER/AGENT. PLEASE HAVE FORM SIGNED.
  
 5) INDICATE SIZE AND LOCATION OF ATTIC
 ACCESS ON PLANS. 97 SBC 2309.6
  
 6) IN ONE SET OF PLANS, SHEET A-2 IS
 SEALED BUT NOT SIGNED AND DATED BY THE
 DESIGN PROFESSIONAL.
  
 7) THE MEAN ROOF HEIGHT OF THE STRUCTURE
 IS 18 FT. NOT 15 FT. PLEASE INDICATE
 MEAN ROOF HEIGHT (VERTICLE DISTANCE FROM
 GRADE TO A POINT AT THE AVERAGE HEIGHT
 OF THE HIGHEST ROOF HAVING A PITCH) ON
 THE PLANS AND CORRECT THE INFORMATION ON
 THE DESIGN COMPLIANCE FORM TO REFLECT AN
 18 FT. MEAN ROOF HEIGHT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202