Plan Review Notes
Plan Review Notes For Permit 01051385
Permit Number 01051385
Review Stop E
Sequence Number 1
Notes
Date Text
2001-06-06 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE MISSING GFI OUTLET
 FOR GARAGE. PER 210-52G
  
 2)NOTE: PLEASE NOTE MISSING OUTLET FOR
 MASTER HALL PER 210-52H
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
 IN GARAGE /ALSO MISSING REQ`D LIGHT.
  
 4) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 NUMEROUS LOCATIONS SHOW "J" FOR JUNCTION
 BOX WHERE LIGHT FIXTURES ARE REQ`D??
  
 5) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
 FRONT RECEPT.
  
 6) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 AIC RATING IS SHOWN FOR PANEL BUT NOT
 FOR MAIN DISCONNECT. PER 110-9/215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372