| Plan Review Notes For Permit 01051385 |
| Permit Number |
01051385 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-06 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE MISSING GFI OUTLET | | | FOR GARAGE. PER 210-52G | | | | | | 2)NOTE: PLEASE NOTE MISSING OUTLET FOR | | | MASTER HALL PER 210-52H | | | | | | 3) PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | | MECHANICAL CODE. | | | IN GARAGE /ALSO MISSING REQ`D LIGHT. | | | | | | 4) PLEASE NOTE EITHER MISSING EGRESS | | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | | PER 210-70 OF THE NEC. | | | NUMEROUS LOCATIONS SHOW "J" FOR JUNCTION | | | BOX WHERE LIGHT FIXTURES ARE REQ`D?? | | | | | | 5) PLEASE NOTE MISSING OUTLET(S) REQ`D | | | BY 210-52E OF THE NEC. | | | FRONT RECEPT. | | | | | | 6) PLEASE CLARIFY EQUIPMENT GROUNDING | | | METHOD BETWEEN FIRST MEANS OF DISCONNECT | | | AND PANEL(S). EQUIPMENT GROUNDING | | | CONDUCTORS ARE TO BE SIZED BY 250-122. | | | | | | 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | AIC RATING IS SHOWN FOR PANEL BUT NOT | | | FOR MAIN DISCONNECT. PER 110-9/215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|