| 2001-07-03 00:00:00 | CHECKLIST: |
| | 1-PLEASE FILE NOTICE OF COMMENCEMENT. |
| | 2-PLEASE PAY IMPACT FEES TO PALM BCH CO. |
| | 3-UPDATE SHEET C-1. SEE COMMENTS. |
| | 4-SHEET A-1 IS MISSING SPECIFICATIONS |
| | FOR CONCRETE SLAB. |
| | 5-PROVIDE ATTIC ACCESS. SECTION 2309.6 |
| | SBC 1997. |
| | 6-REVISE THE DESIGN CERTIFICATION FOR |
| | BUILDING CODE COMPLIANCE FORM. THE |
| | MEAN ROOF HEIGHT IS INCORRECT (18'-6" |
| | +/- ). REVISE VELOCITY PRESSURE |
| | ACCORDINGLY. TABLE 1606.2A SBC 1997. |
| | 7-SOIL TEST REPORT TO HAVE ORIGINAL SEAL |
| | SIGNATURE AND DATE. CHAPTER 471 FL. ST |
| | 8-PROVIDE PRODUCT APPROVAL FOR: |
| | A)GLASS BLOCK DRAWINGS ARE NOT LEGIBLE. |
| | B)SLIDING GLASS DOOR WITH TRANSOM ABOVE |
| | SINGLE ASSEMBLY AS SHOWN ON PLANS. |
| | C)WINDOW MULLIONS. |
| | D)FIXED WINDOWS WITH SIZES AS SHOWN ON |
| | ARCHITECT'S PLANS. |
| | E)PGT ENGINEER TO SIGN, SEAL AND DATE |
| | LETTER FOR SHAPED FIXED WINDOWS AS |
| | REQUIRED BY CHAPTER 471 FL STATUTES. |
| | F)ENTRY DOORS DRAWINGS ARE NOT LEGIBLE. |
| | 9-STORM PANELS: |
| | -CLEARLY INDICATE ON APPROVED DRAWINGS |
| | THE SPECIFIC MOUNTING CONDITIONS AND |
| | ANCHOR TO BE USED ACCORDING TO THE |
| | MEAN ROOF HEIGHT, DESIGN PRESSURES, |
| | EDGE DISTANCE, PANEL SPAN, CONNECTION |
| | TYPE AND STRUCTURE TO BE ATTACHED TO |
| | (NOTE: THIS STRUCTURE IS MASONRY, NOT |
| | CONCRETE). |
| | -REVISE INSTALLATION SCHEDULE ANCHOR |
| | SPACING TO REFLECT CONDITIONS ABOVE. |
| | 10-PROVIDE SURVEY WITH ORIGINAL SEAL, |
| | SIGNATURE AND DATE. |