2001-07-03 00:00:00*************BUILDING UNSAT*************
  
 1) THE SIGNATURE OF THE OWNER/AGENT IS
 REQUIRED ON THE ENERGY FORM 600C-97.
  
 2) ADDITIONAL INFORMATION IS REQUIRED
 FROM THE ENGINEER. PROVIDE POSITIVE AND
 NEGATIVE WIND PRESSURES FOR WINDOW
 OPENING IN STRUCTURE. PROVIDE WIND LOADS
 FOR GLAZING PER 97 SBC 2405.3. THE
 LETTER FROM ENGINEER MUST STATE THAT THE
 INSTALLATION WILL COMPLY WITH THE
 WINDLOAD REQUIREMENTS OF SECTION 1606 OF
 THE STANDARD BUILDING CODE (110MPH) OR
 ASCE 7-95 (145MPH).
  
 3) PROVIDE PRODUCT APPROVALS OR
 ENGINEERING FOR THE FRONT DOOR.
  
 4) PROVIDE INSTALLATION SCHEDULE FOR
 STORM PANELS. INDICATE INSTALLATION
 METHOD AND ANCHOR TYPE THAT WILL BE USED
 FOR PANELS.
  
 5) PROVIDE LOAD & UPLIFT CALCULATIONS
 AND ANALYSIS FOR STEEL BEAM, TRUSSES AND
 2X6 RAFTERS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202