2001-06-28 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) STRUCTURE IS LOCATED IN AN"A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 3) THE ROOF FRAMING PLAN LOCATED ON
 SHEET 3 IS A REVERSE OF THE OTHER
 DRAWINGS SUBMITTED. PLEASE CORRECT.
  
 4) DETAIL A ON SHEET 3 IS NOT SHOWN.
  
 5) PROVIDE DETAIL OF CANTILEVERED BEAM
 REINFORCEMENT AT LANAI.
  
 6) PROVIDE (2) COPIES OF INSTALLATION
 SCHEDULE AND KEY PLAN FOR STORM PANELS.
  
 TRUSSES
 UNSAT
  
 1) THE MEAN ROOF HEIGHT GIVEN ON TRUSS
 DRAWINGS IS NOT CONSISTENT. H7A HAS
 11.73 FT.,HJ1 HAS 15FT,HJ5 HAS 15.8FT.,
 ETC. PLEASE CORRECT.
  
 2) DRAWINGS LIST SBCCI 97, SOUTHERN
 BUILDING CODE CONGRESS INTERNATIONAL IS
 THE NAME OF THE ORGINAZATION NOT THE
 ACTUAL MODEL CODE, WHICH IS THE 1997
 STANDARD BUILDING CODE OR 97 SBC. PLEASE
 CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202