| Plan Review Notes For Permit 01051240 |
| Permit Number |
01051240 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-28 00:00:00 | *************BUILDING UNSAT************* | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) STRUCTURE IS LOCATED IN AN"A" FLOOD | | | ZONE. A FLOOD ELEVATION CERTIFICATE WILL | | | BE REQUIRED. | | | | | | 3) THE ROOF FRAMING PLAN LOCATED ON | | | SHEET 3 IS A REVERSE OF THE OTHER | | | DRAWINGS SUBMITTED. PLEASE CORRECT. | | | | | | 4) DETAIL A ON SHEET 3 IS NOT SHOWN. | | | | | | 5) PROVIDE DETAIL OF CANTILEVERED BEAM | | | REINFORCEMENT AT LANAI. | | | | | | 6) PROVIDE (2) COPIES OF INSTALLATION | | | SCHEDULE AND KEY PLAN FOR STORM PANELS. | | | | | | TRUSSES | | | UNSAT | | | | | | 1) THE MEAN ROOF HEIGHT GIVEN ON TRUSS | | | DRAWINGS IS NOT CONSISTENT. H7A HAS | | | 11.73 FT.,HJ1 HAS 15FT,HJ5 HAS 15.8FT., | | | ETC. PLEASE CORRECT. | | | | | | 2) DRAWINGS LIST SBCCI 97, SOUTHERN | | | BUILDING CODE CONGRESS INTERNATIONAL IS | | | THE NAME OF THE ORGINAZATION NOT THE | | | ACTUAL MODEL CODE, WHICH IS THE 1997 | | | STANDARD BUILDING CODE OR 97 SBC. PLEASE | | | CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|