| Plan Review Notes For Permit 01051238 |
| Permit Number |
01051238 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-29 00:00:00 | *************BUILDING UNSAT************* | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) STRUCTURE IS LOCATED IN AN "A" FLOOD | | | ZONE. AN ELEVATION CERTIFICATE WILL BE | | | REQUIRED. | | | | | | 3) THE ROOF FRAMING PLAN LOCATED ON | | | SHEET 3 IS A REVERSE OF THE OTHER | | | DRAWINGS SUBMITTED. PLEASE CORRECT. | | | | | | 4) DETAIL A ON SHEET 3 IS NOT SHOWN. | | | | | | 5) PROVIDE DETAIL OF CANTILEVERED BEAM | | | REINFORCEMENT AT LANAI. | | | | | | 6) PROVIDE (2) COPIES OF INSTALLATION | | | SCHEDULE AND KEY PLAN FOR STORM PANELS. | | | | | | 7) OWNER/AGENT SIGNATURE IS REQUIRED ON | | | ENERGY CALCULATIONS. | | | | | | TRUSSES | | | UNSAT | | | | | | 1) THE MEAN ROOF HEIGHT GIVEN ON TRUSS | | | DRAWINGS IS NOT CONSISTENT. MEAN ROOF | | | HEIGHT OF STRUCTURE IS 15 FT. PLEASE | | | CORRECT. | | | | | | 2) DRAWINGS REFERENCE 97 SBCCI, WHICH IS | | | THE ORGANIZATION. THE 97 SBC (STANDARD | | | BUILDING CODE) IS THE MODEL CODE THAT | | | SHOULD BE REFERENCED. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|