Plan Review Notes
Plan Review Notes For Permit 01051238
Permit Number 01051238
Review Stop R
Sequence Number 1
Notes
Date Text
2001-06-29 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 3) THE ROOF FRAMING PLAN LOCATED ON
 SHEET 3 IS A REVERSE OF THE OTHER
 DRAWINGS SUBMITTED. PLEASE CORRECT.
  
 4) DETAIL A ON SHEET 3 IS NOT SHOWN.
  
 5) PROVIDE DETAIL OF CANTILEVERED BEAM
 REINFORCEMENT AT LANAI.
  
 6) PROVIDE (2) COPIES OF INSTALLATION
 SCHEDULE AND KEY PLAN FOR STORM PANELS.
  
 7) OWNER/AGENT SIGNATURE IS REQUIRED ON
 ENERGY CALCULATIONS.
  
 TRUSSES
 UNSAT
  
 1) THE MEAN ROOF HEIGHT GIVEN ON TRUSS
 DRAWINGS IS NOT CONSISTENT. MEAN ROOF
 HEIGHT OF STRUCTURE IS 15 FT. PLEASE
 CORRECT.
  
 2) DRAWINGS REFERENCE 97 SBCCI, WHICH IS
 THE ORGANIZATION. THE 97 SBC (STANDARD
 BUILDING CODE) IS THE MODEL CODE THAT
 SHOULD BE REFERENCED. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202