| Plan Review Notes For Permit 01051204 |
| Permit Number |
01051204 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-10-13 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) ACCORDING TO SPC-94 TABLE 407 | | | 4 MALE W/C'S AND 4 FEMALE W/C'S ARE | | | REQUIRED. 2 URNALS CAN REPLACE 1/2 OF | | | W/C'S REQUIRED (4). PLEASE SHOW REQUIRED | | | FIXTURES FOR 7,554 @ 70SF PER PERSON = | | | 108 PEOPLE. | | | | | | 2) WATER HAMMER ARRESTORS SHALL BE | | | PLACED CLOSE TO SOURCE NOT AT TOP OF | | | DROP AS SHOWN PER WH-PDI 201 AND MAN- | | | UFACTURES INSTALLATION INSTRUCTIONS. | | | PAGE P5.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|