Plan Review Notes
Plan Review Notes For Permit 01051204
Permit Number 01051204
Review Stop P
Sequence Number 3
Notes
Date Text
2001-10-13 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) ACCORDING TO SPC-94 TABLE 407
 4 MALE W/C'S AND 4 FEMALE W/C'S ARE
 REQUIRED. 2 URNALS CAN REPLACE 1/2 OF
 W/C'S REQUIRED (4). PLEASE SHOW REQUIRED
 FIXTURES FOR 7,554 @ 70SF PER PERSON =
 108 PEOPLE.
  
 2) WATER HAMMER ARRESTORS SHALL BE
 PLACED CLOSE TO SOURCE NOT AT TOP OF
 DROP AS SHOWN PER WH-PDI 201 AND MAN-
 UFACTURES INSTALLATION INSTRUCTIONS.
 PAGE P5.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377