| Plan Review Notes For Permit 01051204 |
| Permit Number |
01051204 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-08-30 00:00:00 | DENIED | | | | | | CODE REFEREMCES - SPC-94 - FACBC-97 | | | | | | 1) COMMENT #1 FROM PREVIOUS REVIEW NOT | | | ADDRESSED. ALSO ONLY ONE DRINKING FOUN- | | | TAIN SHOWN, THREE REQUIRED PER SPC-94 | | | TABLE 407. | | | | | | 2) COMMENT #2 FROM PREVIOUS REVIEW NOT | | | ADDRESSED. | | | | | | 3) PAGE P5-1 WATER RISER DIAGRAM, IN- | | | STALL WATER HAMMER ARRESTORS ACCORDING | | | TO MANUFACTURE'S INSTALLATION INSTRUCT- | | | IONS AND PDI-WH 201. | | | | | | 4) SUBMIT DETAIL ON WATER HEATER BY MOP | | | SINK IN JANITOR'S ROOM. | | | | | | 5) PAGE P5-1 SANITARY RISER DIAGRAM, | | | ELECTRIC WATER COOLER BY CARILLON STAIRS | | | NOT SHOWN. ALSO FLOOR DRAIN BY MOP SINK | | | NO SHOWN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|