| Plan Review Notes For Permit 01051204 |
| Permit Number |
01051204 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-09-05 00:00:00 | *******************DENIED*************** | | | | | | | | | AS PER 1997 SMC 607.1, DUCTS LOCATED | | | UNDER CONCRETE SHALL BE OF METAL OF | | | SUFFICIENT STRENGTH ENCASED ON ALL SIDES | | | WITH NOT LESS THAN 2" OF CONCRETE OR | | | OTHER APPROVED MATRIAL SPECIFICALLLY | | | DESIGNED FOR THIS SERVICE IN ACCORDANCE | | | WITH MANUFACTURER'S RECOMMENDATIONS. | | | | | | DAMPERS INDICATED ON BRANCH LINE OFF THE | | | 18" X 18" AND 18" X 12" SHALL BE | | | ACCESSIBLE. | | | | | | | | | NOTE:10' CLEARANCE BETWEEN ANY EXHAUST | | | AND FRESH AIR INTAKES. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388 |
|