Plan Review Notes
Plan Review Notes For Permit 01051204
Permit Number 01051204
Review Stop M
Sequence Number 2
Notes
Date Text
2001-09-05 00:00:00*******************DENIED***************
  
  
 AS PER 1997 SMC 607.1, DUCTS LOCATED
 UNDER CONCRETE SHALL BE OF METAL OF
 SUFFICIENT STRENGTH ENCASED ON ALL SIDES
 WITH NOT LESS THAN 2" OF CONCRETE OR
 OTHER APPROVED MATRIAL SPECIFICALLLY
 DESIGNED FOR THIS SERVICE IN ACCORDANCE
 WITH MANUFACTURER'S RECOMMENDATIONS.
  
 DAMPERS INDICATED ON BRANCH LINE OFF THE
 18" X 18" AND 18" X 12" SHALL BE
 ACCESSIBLE.
  
  
 NOTE:10' CLEARANCE BETWEEN ANY EXHAUST
 AND FRESH AIR INTAKES.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388