Plan Review Notes
Plan Review Notes For Permit 01051204
Permit Number 01051204
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-08-20 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 2) PLEASE PROVIDE FLAME SPREAD
 INFORMATION FOR SEATING.
 3) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH FIRE SPRINKLER DRAWINGS.
 4) PLEASE INDICATE PROVISIONS FOR
 TWO HANDICAPPED PERSONS. PLEASE SHOW
 SEATING FOR TWO HANDICAPPED PERSONS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910