Plan Review Notes
Plan Review Notes For Permit 01051204
Permit Number 01051204
Review Stop B
Sequence Number 2
Notes
Date Text
2001-09-07 00:00:00PLAN REVIEW # 01051204
 901 S FLAGLER
 74.43.43.27.25.000.0010.
 SCHWAB, TWITTY & HANSER
 TEL (561) 832-5599
 FAX (561) 832- 4828
  
 SBC = 1997 STANDARD BUILDING CODE
 SBC* = COUNTYWIDE AMENDMENTS TO THE 1997
 STANDARD BUILDING CODE
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
 1997 EDITION
 FL BLD CODE 2001 = FLORIDA BUILDING CODE
 2001 EDITION/ ADOPTED JAN.1/2002
 BUILDINGS THAT APPLY FOR A PERMIT
 AFTER DEC. 31, 2001WILL BE REVIEW
 ED UNDER THE 2002 CODE.
  
 1)- SBC 104.2.2. CITY ADMINISTRATIVE
 CODE, ADDITIONAL INFORMATION REQUIRED.
  
 2)- CHAPTER 553 FL STATUTE, CHAPTER 468
 & CHAPTER 7 CITY CODE. THIS BUILDING
 QUALIFIES AS A THRESHOLD BUILDING, A
 THRESHOLD INSPECTOR WILL NEED TO REGIST-
 ER WITH ASST. BUILD. OFF. DON NEELY. THE
 ENFORCEMENT AGENCY SHALL REQUIRE A SPEC-
 IAL INSPECTOR TO PREFORM STTRUCTURAL IN-
 SPECTIONS ON A THRESHOLD BUILDING PURSU-
 ANT TO A STRUCTURAL INSPECTION PLAN PRE-
 PARED BY THE ENGINEER OR ARCHITECT OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO AND APPROVED BY THE
 ENFORCEMENT PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING. TTHE PURPOSE OF
 THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES &
 SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR THE COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3)- SBC 104.2.2. ADD INFORMATION RE-
 QUESTED, FL ACC CODE SS.503.505 CHAP
 97-76. THE BUILDING DEPARTMENT REQUEST A
 LETTER FROM PALM BEACH ATLANTIC COLLEGE
 INDICATING THE " USAGE OF THE CHAPEL".
 THE STATE STATUTES INDICATE THAT BUILD-
 INGS INTENDED FOR THE CONGREGATION TO
 GATHER FOR THE PREFORMANCE OF RELIGIOUS
 CEREMONIES, ARE EXEMPT FROM ACCESSIBIL-
 ITIY REQUIREMENTS, (VERTICAL ACCESSIBIL-
 ITY). THE PLANS INDICATE THAT THE PLANS
 (A.2.1) INDICATE THAT THE SEATS WILL BE
 REMOVAL BY OWNER ALLOWING FOR VARIOUS
 EVENTS TO TAKE PLACE IN THIS BUILDING.
  
 4)- CHAPEL SQ. FT.= 4362 SQ FT @ 7 SQ FT
 NER PERSON + OCCUPANT LOAD OF 624 PEOPLE
 THIS OCCUPANT LOAD QUALIFIIES THIS BUILD
 ING AS A THRESHOLD BUILDING.
  
 5)- ARCH. PLANS A.1.2. CODE REVIEW STATE
 MENT INDICATES THIS BUILDING IS A
 TYPE V FULLY SPRINKLERED BUILDING,UNPRO-
 TECTED, WITH A MAXIMUM HEIGTH OF 55'-0.
 THE MEAN ROOF HEIGTH, SHEET A.3.5. GIVEN
 THE BEAM @ THE UPPER ROOF LINE IS 56'-0"
 AND SCALING THE CENTERLINE OF THE TRUSS
 A HEIGTH OF 8'-6" IS DERIVED, 1/2 THIS
 HEIGTH OR 4'-3" PLUS THE BEAM HEIGTH OF
 56'-0" GIVES US THE MEAN ROOF HEIGTH OF
 60'-3". THIS BY TABLE 500 A-2 SMALL
 ASSEMBLY WOULD HAVE TO BE A 1-HR PROTECT
 ED TO QUALIFY FOR THE ADDITIONAL FOOTAGE
 THIS MEAN ROOF HEIGTH COULD GO TO A
 HEIGTH OF 65'-0". THIS ALSO REFLECTS IN
 TABLE 600 AS TO THE STRUCTURAL MEMBRS
 AN THE RATING REQUIRED UNDER TABLE 600.
  
 6)- SHEET A.2.1 NOTE MOVABLE SEATS BY
 OWNER, SBC 1019.10.1.4. SEATS SHALL BE
 FASTENED TO THE FLOOR IN ALL ASSEMBLY
 OCCUPANCIES WITH OCCUPANT LOADS GREATER
 THAN 200.
  
 7)- SHEET A.2.1. DOOR 117 C THE PLANS
 ARE NOT CLEAR IF THERE IS A STEP AT THE
 EXTERIOR? SBC 1013.1 RAMPS ARE TO BE
 USED WHEN THE DIFFERENCE IN ELEVATION IS
 12 INCHES OR LESS.
  
 8)-MISSING INFORMATION FROM SBC TABLE
 803.3. MINIMUM INTERIOR FINISH CLASSIF-I
 CATION.
  
 9)- MISSING SOILS REPORT, MINIMUM BEAR-
 ING VALUE, SBC * 1804.2
  
 10)- INDICATE THE VELOCITY PRESSURES FOR
 WINDOWS & DOORS, INCLUDE INTERIOR AND
 END ZONE PRESSURES.
  
 11)- COMPONENTS & CLADDING
 A)- WINDOW & DOOR BUCK ATTACHMENT
 B)- PRODUCT APPROVALS FOR ALL GLAZED
 OPENINGS, SBC 1606.4.1./ 1707.4.1*.
 GLAZED OPENINGS WILL REQUIRE LARGE MIS-
 SLE IMPACT RESISTANT GLAZING. STANDARDS
 FOR WINDBORNE DEBRIS IMPACT TEST
 SSTD-12-97/ CITY INTERPITTATION.
 C)- DOORS WILL ALSO REQUIRE PRODUCT TEST
 ING (EXTERIOR) SBCCI OR DADE COUNTY RE-
 PORTS ARE ACCEPTED.
  
 12)- SBC1503.3.2 ROOFING SYSSTEMS SHALL
 BE DESIGNED TO WITHSTAND THE APPROPRIATE
 WINDLOADS. THE NAILING DETAIL PROVIDED
 ON SHEET S-3 INDICATES NAILING REQUIRE-
 MENTS FOR LESS THAN 25'.THE COUNTY AMEND
 MENTS GIVES NAILING PATERNS TO 35'.ABOVE
 THIS THE STRUCTURAL ENGINEER WILL HAVE
 TO GIVE THE PATTERN & TYPE OF FASTENER.
 FOR THE STEEL DECK AS WELL AS THE PLY-
 WOOD FASTENED TO THE STEEL DECKING.
 PRODUCT APPROVALS WILL BE REQUIRED
 FOR THE TYPE OF ROOFING SYSTEMSTHAT
 WILL BE APPLIED AS THE FINISH ROOF.
  
 13)- FIRE DISTRICT SBC F102.2: ROOF
 COVERINGS IN A FIRE DISTRICT SHALL CON-
 FORM TO THE REQUIREMENTS OF A CLASS
 "A" OR "B" ROOF.
  
 14)- FIRE DISTRICT ; F102.2 11 PLASTIC
 VENEERS NOT PERMITED IN A FIRE DISTRICT
 SBC 103.7 ALTERNATE MATERIALS & METHODS
 SHOW COMPLIANCE.
  
 15)- SHEET A-6.3 SECTION DETAIL #3 INDI-
 CATES A HORIZONTAL STEEL BEAM OF TUBE
 STEEL WITH SOME TYPE OF MATERIAL BELOW
 THAT IS NOT INDICATED? TYPE V BUILDING!
  
 16)- THIS SAME UPPER ROOF DETAIL DOESN'T
 SHOW UP ON THE STRUCTURAL DRAWINGS
 S-3 NOR S-4, ELE.56"-0".?
  
 17)- SHEET A6.6 DETAILS 1,3&7 DEPICT
 CAST STONE BANDING. SBC 1403.2.7 ATTACH-
 MENT
  
 18)- SHEET A.3.9. DETAIL #2 PRECAST PAN-
 ELS, ATTACHMENT PER SBC 1403.2.6.
  
 19)- M2.1 DEPICTS DUCTS UNDER THE FLOOR
 AT PLATFORM LEVEL. S-1 DETAILS 5&6 TUN-
 NEL FOR DUCT RUNS, DETAIL #6 INDICATES
 A 12"X10" DUCT(BRANCH) THE MAIN TRUNK
 LINE IS AS BIG AS 24"X18" WILL THE TUN-
 NEL INDICATES THAT IT IS 2'-0" WIDE WILL
 IT BE WIDER? ALSO THE HEIGTH OF THE
 BUILDING FOUNDATION IS NOT INDICATED ON
 THE PLANS SHOULD IT BE DEEPER TO ACCOM-
 IDATE THE DUCT & TUNNEL?
  
 20)- FL ENERGY CODE CALCULATIONS
  
 21)- COUNTY IMPACT FEES TO BE PAID,
 CHECK FOR CREDITS BUILDING THAT WAS
 DEMOLISHED!
  
 22RADON FEES / $77.02 TO CITY
  
 PLEASE RESPOND WITH A WRITTEN STATEMENT
 TO WHERE I CAN FIND THE ADDITIONAL INFOR
 MATION, THIS WILL SPEED UP THE PLAN RE-
 RIEW PROCESSTHANK YOU FOR ALL YOUR
 HELP IN THESE MATTERS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X 8412