| 2001-06-10 00:00:00 | PLUMBING PLAN REVIEW"DENIED" |
| | CODE REFERENCES SPC 94, FACBC 97. |
| | (1) SHT A2.1 PROVIDE CALCULATIONS FOR |
| | MIN FACILITIES,TAB 407,SHOW LOCATION OF |
| | DRINKING FOUNTAINS. "376 PERSONS" |
| | (2) SHT A2.4 PROVIDE CALCULATIONS FOR |
| | ROOF DRAINAGE ,ISOMETRIC DRWG WITH PIPE |
| | SIZES, PRIMARY,SECONDARY SEC 1109.2 |
| | SEPERATE SYSTEMS. SEC 104.3 |
| | (3)SHTA4.1 TOILET RM'S 104,121,COMPLY W/ |
| | FACBC 97,FIG 30(E) THE LAVATORY SHALL |
| | NOT ENCROACH INTO THE CLEAR FOOR SPACE |
| | FOR THE WATER CLOSET.FLUSH CONTROLS ON |
| | MOUNTING SIDE SEC 4.16.5 |
| | 4) SHT P0.1, PLBG NOTES #13 AIR CHAMBERS |
| | PROVIDE A DETAIL OF A RECHARGEABLE AIR |
| | CHAMBER AND SIZE. |
| | (5) SHT P2.1, PROVIDE A ISOMETRIC DRWG. |
| | OF DWV SYSTEM,SHOW PIPE SIZES,SEC 104.3 |
| | (6) SHT P2.1, FLOOR DRAINS IN PUBLIC |
| | REST RM'S,TRAP PRIMERS REQ. SEC 409.4 |
| | (7) SHT P3.1, DOMESTIC WATER, PROVIDE |
| | ISOMETRIC DRWG. SHOW PIPE SIZES,SEC 104. |
| | NO MORE THAN 2 C/W FIXTURES ON 1/2". |
| | NO MORE THAN 4 H/W FIXTURES ON 1/2". |
| | PALM BCH CNTY AMENDMENTS TO SPC 94. |
| | END OF COMMENTSPAUL SCHMITZ |