| Plan Review Notes For Permit 01051204 |
| Permit Number |
01051204 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-11 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | | AHRAE 62-89 AND AIR BALANCE SCHEDULE | | | FOR COMPLIANCE WITH 1997 SMC 501.2. | | | | | | 2.PLEASE PROVIDE ALL EQUIPMENT | | | INFORMATION. | | | | | | 3.PROVIDE LOCATIONS OF ANY FIRE/SMOKE | | | DAMPERS AS WELL AS ANY DUCT SMOKE | | | DETECTORS. | | | | | | 4.MISSING PLANS ACCORDING TO INDEX | | | OF DRAWINGS. (4 DRAWINGS SUBMITTED | | | OUT OF 13). | | | | | | 5.DRAWING M6.1 UNDER FAN SCHEDULE- | | | GENERAL FAN NOTES: #7. INDICATES | | | KITCHEN HOOD/EQUIPMENT.ADDITIONAL | | | MECHANICAL PLANS & PERMIT REQUIRED | | | FOR HOOD AND FIRE SUPRESSION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT.8388. |
|