2001-06-07 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 2) DUCT SMOKE DETECTORS REQUIRED IN
 HVAC SYSTEMS OVER 2000 CFM.
 3) NO COMBUSTIBLES ABOVE CEILING IF THIS
 AREA IS USED AS A RETURN AIR PLENUM.
 4) PANIC HARDWARE REQUIRED ON ALL EXIT
 DOORS.
 5) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS. ALSO FLAME SPREAD
 INFORMATION REQUIRED FOR SEATING.
 6) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH FIRE SPRINKLER DRAWINGS.
 7) PLANS NOT SIGNED AND SEALED.
 8) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 9) PLEASE BE ADVISED THAT THE BUILDING
 WILL BE LOCATED IN THE CITY FIRE LIMITS.
 COMPLIANCE WITH APPENDEX F "FIRE
 DISTRICT" PER SBC 1997 IS REQUIRED.
 10) SEVERAL ELECTRICAL DRAWINGS ARE
 MISSING. PLEASE CLEARLY INDICATE ALL
 ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHT FIXTURES WITHIN THE CHAPEL.
 11) PLEASE INDICATE TYPE OF CONSTRUCTION
 FOR PLATFORM.
 12) STAIRS TO COMPLY WITH NEW STAIR
 REQUIREMENTS PER NFPA 101, THE LIFE
 SAFETY CODE.
 13) A KNOX-BOX RAPID ENTRY SYSTEM WILL
 BE REQUESTED FOR THE BUILDING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910