| 2001-06-07 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY |
| | CODE 3343-00. |
| | 2) DUCT SMOKE DETECTORS REQUIRED IN |
| | HVAC SYSTEMS OVER 2000 CFM. |
| | 3) NO COMBUSTIBLES ABOVE CEILING IF THIS |
| | AREA IS USED AS A RETURN AIR PLENUM. |
| | 4) PANIC HARDWARE REQUIRED ON ALL EXIT |
| | DOORS. |
| | 5) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION INFORMATION FOR WALLS |
| | AND CEILINGS. ALSO FLAME SPREAD |
| | INFORMATION REQUIRED FOR SEATING. |
| | 6) NO HYDRAULIC CALCULATIONS PROVIDED |
| | WITH FIRE SPRINKLER DRAWINGS. |
| | 7) PLANS NOT SIGNED AND SEALED. |
| | 8) PROVISIONS ARE TO BE MADE FOR AT |
| | LEAST TWO HANDICAPPED PERSONS. |
| | 9) PLEASE BE ADVISED THAT THE BUILDING |
| | WILL BE LOCATED IN THE CITY FIRE LIMITS. |
| | COMPLIANCE WITH APPENDEX F "FIRE |
| | DISTRICT" PER SBC 1997 IS REQUIRED. |
| | 10) SEVERAL ELECTRICAL DRAWINGS ARE |
| | MISSING. PLEASE CLEARLY INDICATE ALL |
| | ILLUMINATED EXIT SIGNS AND EMERGENCY |
| | LIGHT FIXTURES WITHIN THE CHAPEL. |
| | 11) PLEASE INDICATE TYPE OF CONSTRUCTION |
| | FOR PLATFORM. |
| | 12) STAIRS TO COMPLY WITH NEW STAIR |
| | REQUIREMENTS PER NFPA 101, THE LIFE |
| | SAFETY CODE. |
| | 13) A KNOX-BOX RAPID ENTRY SYSTEM WILL |
| | BE REQUESTED FOR THE BUILDING. |
| | |
| | CAPTAIN MIKE CARSILLO |
| | 659-8096,EXT.8497 |
| | 835-2910 |