Plan Review Notes
Plan Review Notes For Permit 01051204
Permit Number 01051204
Review Stop B
Sequence Number 1
Notes
Date Text
2001-07-02 00:00:00 
 14)- SHEET A-6.3 SECTION 2-3. THESE
 DETAILS DEPICT TUBE STEEL CHANNELS BUT
 INFORMATION FOR THESE PERTICULAR DETAILS
 DO NOT REFLECT WHAT THE FINISH CEILING
 MATERIAL WILL BE NOR DOES THE PLANS IN-
 DICATE WHAT TYPE OF MATERIAL IS DIRECTLY
 ABOVE THIS SITUATED BETWEEN THE FINISH
 CEILING AND THE BATT INSULATION.
  
 15)- SHEET A-6.3 SECTION DETAIL #3 INDI-
 CATES A HORIZONTAL STEEL BEAM OF TUBE
 STEEL WITH SOME TYPE OF MATERIAL BELOW
 WHICH IS NOT INDICATED.
  
 16)- THIS SAME DETAIL DOES NOT SHOW UP
 ON THE STRUCTURAL DRAWINGS NOR DOES THE
 STUCTURAL DRAWINGS GIVE US THE CONCRETE
 BEAM INFORMATION FOR WALL ON THE UPPER
 OR HIGH ROOF PLAN.
  
 17)- SBC TABLE 600 TYPE II BUILDING:
 ROOFS/ ROOF CEILING ASSEMBLIES (FOOTNOTE
 "E") FIRE RETARDANT TREATED WOOD MAY BE
 USED TRUSSES, LEDGERS & PLYWOOD.
  
 18)- CORRECT PLAYWOOD TO PLYWOOD.
  
 19)- SBC 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION SCHEDULE FOR ALL ROOMS.
  
 20)- SBC 1204.2 PUBLIC RESTROOMS, ARE TO
 HAVE NONABSORBENT MATERIALS ON THE FLOOR
 & WALLS TO A HEIGTH OF 4"-0".
  
 21)-S-7 THE SCHEDULES ARE MISSING
 VITAL INFORMATION FOTTING SCHEDULE INCOM
 PLETE, COLUMN SCHEDULE NOT FILLED IN,
 BEAM SCHEDULE INCOMPLETE, DESIGN LOAD
 SCHEDULE NOT FILLED IN!!!!!!!!!!!!!!!!!
  
 22)- SHEET A.2.1THE ORGAN STAIRS AS
 WELL AS THE PIANO STAIRS REQUIRES HAND-
 RAILS ON EACH SIDE, SBC 1007.5.2.
  
 23)- SHEET A.5.2 DETAIL #2 SANCTUARY
 STAIRS DEPICT 4 RISERS AT APPR.7" AND
 1 STAIR AT APPROX. 14", SBC 1007.3.1.
  
 24)- A THROUGH PLAN EVIEW CANNOT BE
 ACCOMPLISHED AT THIS TIME, THE PLANS
 NEED TO BE REVIEWED BY THE DESIGN PROFES
 SIONALS TO CORRECT ALL DEFICENCIES THAT
 ARE LISTED AND THOUGH THATARE NOT LIST
 ED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 PHONE (561) 659-8096 EX8412
2001-06-29 00:00:00PLAN REVIEW- 01051204
 310 OKEECHOBEE BLVD
 74-43-43-27-24-000-0010
 STH ARCHITECTURAL GROUP INC.
 PH. (561) 832-5599
 FAX (561) 655-4828
  
 1)- FL STATE SATUTE 481 REQUIRES ARCHI-
 TECTS TO SIGN & SEAL PLANS FOR PUBLIC RE
 CORD.
  
 2)- SBC 104.2.2 CITY AMENDMENTS- SURVEY
 SIGNED & SEALED, LESS THAN A YEAR OLD.
  
 3)- CHAPTER553 FL STATUTE, CHAPTER 468
 & CHAPTER 7 CITY CODE, THIS BUILDING IS
 A THRESHOLD BUILDING, A THRESHOLD INSPEC
 TOR WILL NEED TO REGISTER WITH ASST
 BUILDING OFFICIAL DON NEELY. THE ENFORC-
 ING AGENCY SHALL REQIURE A SPECIAL
 INSPECTOR TO PREFORM STRUCTURAL INSPEC-
 TIONS ON A THRESHOLD BUILDING PURSUANT
 TO A STRUCTURAL INSPECTION PLAN PREPARED
 BY THE ENGINEER OR ARCHITECT OF RECORD.
 THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO AND APPROVED BY THE ENFORC-
 ING AGENCY PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FFOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING. THE PURPOSE OF
 THE STRUCTURAL INSPECTION PLAN IA TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES &
 SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR THE COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 4)- FL ACCESSIBILITY CODE: SS 553.505
 CH. 97-76. THE BUILDING DEPARTMENT RE-
 QUEST A LETTER FROM PALM BEACH ATLANTIC
 COLLEGE INDICATING THE "USAGE OF THE
 CHAPEL". STATE STATUTES INDICATE THAT
 BUILDINGS INTENDED FOR THE CONGREGATION
 TO GATHER FOR THE PERFORMANCE OF
 RELIGIOUS RECEMONIES,ARE EXEMPT FROM
 ACCESSIBILITY REQUIREMENTS.
  
 5)- CHAPEL SQ.FT. 4362 SQ.FT. @ 7 SQ/PER
 OCC.LOAD=624 PRSONS. THRESHOLD BUILDING.
  
 6)- CODE CRITERIA:
 THE CITY IS REFRENCING THE 1997 STANDARD
 BUILDING CODE.
 ASCE 7-95 110 MPH
 IMPORTANCE FACTOR : 1.15
  
 7)- MISSING THE MINIMUM INTERIOR
 FINISH CLASSIFICATIONS TABLE 803.3.
  
 8)- MISSING SOILS REPORT SBC 1804.2 AMEN
  
 9)- SBC 1606.1 VELOCITY PRESSURES FOR
 WINDOWS & DOORS ENCLUDE END ZONES.
  
 10)- COMPONENTS & CLADDING
 A) WINDOW & DOOR BUCK ATTACHMENT
 B) PRODUCT APPROVALS FOR ALL GLAZED
 OPENINGS, SBC 1606.4.1/ 1707.4.1
 COUNTY AMENDMENTS/ SEE ATTACHED CITY
 POLICY FOR LARGE PROJECTS. LARGE
 MISSLE IMPACT RESISTANCE, STANDARDS
 FOR WINDBORNE DERIS IMPACT TEST,
 SSTD-12-97.
  
 11)- SBC 1503.3.2 ROOFING SYSTEMS SHALL
 BE DESIGNED TO WITHSTAND THE APPROPRIATE
 WINDLOADS PRESCRIBED IN CHAP. 16/ 110MPH
 SBCCI REPORTS OR DADDE COUNTY PRODUCT
 APPROVAL REPORTS ARE ACCEPTABLE.
  
 12)- FIRE DISTRICT: SBC- F 102.2:
 ROOF COVERINGS INA FIRE DISTRICT SHALL
 CONFORM TO THE REQUIREMENTS OF A CLASS
 "A" OR CLASS "B" ROOF.
  
 13)- FIRE DISTRICT:F 102.2.11PLASTIC
 VENEER NOT PERMITED IN THE FIRE DISTRICT
 SBC 103.7 ALTERNATE MATERIALS & METHODS
 SHOW COMPLIANCE THROUGH REPORT THAT THE
 EXPANDED POLYSTYRENE EXTERIOR MOLDING
 WHEN COVERED WITH THE EFIS SYSTEM HAS
 THE SAME SMOKE & FLAME SPREAD AS FIRE
 RESISTANT TREATED WOOD.