| Plan Review Notes For Permit 01051202 |
| Permit Number |
01051202 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-07 00:00:00 | PLUMBING PLAN REVIEW"DENIED" | | | ROSARIAN ACADEMY MONTESSORI CLASSROOMS | | | (1) SHT A2 REST RM'S IN CLASS RM TO | | | COMPLY W/FACBC-97 SEC 4.22.1 AND SPC 94 | | | TAB 407 MINIMUM FACILITIES, ONLY 1 W/C | | | FOR 1-50 PERSONS, IS REQUIRED. | | | (2) SHT A2 BREAK RM SINK IN STAFF LOUNGE | | | TO COMPLY W/FACBC 97 SEC 4.24 HGTH 34", | | | AND SEC 4.24.5 CLEAR FLR SPACE 30"X48". | | | (3) SHT P1,P2 AIR CHAMBER,GENERAL NOTE | | | #16 COMPLY WSPC 94 SEC 607.8.3 AIR CHAM- | | | BERS TO BE ACCESSIBLE, RECHARGEABLE. | | | (4) SHT P1 WATER PIPE ISOMETRIC,SHOW | | | WHICH LINE IS HOT AND WHICH IS COLD,WITH | | | DASHED LINES.SPC 94 SEC 104.3 | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X 8233 | | | PREVIOUS PHONE CONVERSATION WITH | | | MR. HAMED RODREGREQUEZ832-5599 |
|