Plan Review Notes
Plan Review Notes For Permit 01051202
Permit Number 01051202
Review Stop E
Sequence Number 1
Notes
Date Text
2001-06-07 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT SERVICE METER
 IS SHOWN AT 400A`S, TWO DISCONNECTS AT
 200A`S(FUSED AT 150A EACH) AND SERVICE
 ENTRANCE CONDUCTORS ONLY RATED FOR
 310A`S IN THE 75' COLUMN IN 310-16.
 PLEASE PLACE NOTE ON PLANS THAT FUSE
 RATINGS ARE NOT TO EXCEED SERVICE ENTRA-
 -NCE CONDUCTOR RATINGS.
 2)NOTE:PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATINGS FOR PANELS
 WERE SUBMITTED BUT NOT FOR MAIN DISC`S
  
 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC) PER 215-3 AND
 230-42.
 PLEASE SHOW LOAD CALCUALTIONS. PER 220
  
 4)NOTE: PLEASE SHOW CONDUCTORS SIZES
 FROM METER TO GUTTER AND GUTTER TO MAIN
 DISCONNECTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372