| 2001-06-07 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT SERVICE METER | | | IS SHOWN AT 400A`S, TWO DISCONNECTS AT | | | 200A`S(FUSED AT 150A EACH) AND SERVICE | | | ENTRANCE CONDUCTORS ONLY RATED FOR | | | 310A`S IN THE 75' COLUMN IN 310-16. | | | PLEASE PLACE NOTE ON PLANS THAT FUSE | | | RATINGS ARE NOT TO EXCEED SERVICE ENTRA- | | | -NCE CONDUCTOR RATINGS. | | | 2)NOTE:PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT AIC RATINGS FOR PANELS | | | WERE SUBMITTED BUT NOT FOR MAIN DISC`S | | | | | | 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ETC) PER 215-3 AND | | | 230-42. | | | PLEASE SHOW LOAD CALCUALTIONS. PER 220 | | | | | | 4)NOTE: PLEASE SHOW CONDUCTORS SIZES | | | FROM METER TO GUTTER AND GUTTER TO MAIN | | | DISCONNECTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|