| 2001-06-13 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01051202 | | | 800 N OLIVE AV | | | MJS CONSTRUCTION | | | 615- 9348 | | | | | | STANDARD BUILDING CODE 1997 | | | 1)- SBC 1503.3.2. ALL ROOFING SYSTEMS | | | SHALL BE DESIGNED TO MEET THE WIND ZONE | | | PRESCRIBED IN 1606 (110 MPH), ACCECTABLE | | | PRODUCT APPROVAL REPORTS: SBCCI OR DADE | | | COUNTY. | | | | | | 2)- SBC AMEND. 1606.4/1707.4.1.THE CITY | | | POLICY FOR STORM SHUTTERS REQUIRES A | | | STORM SHUTTER SCHEDULE & KEY PLAN. THE | | | SCHEDULE WILL INCLUDE WALL PRESSURES W/E | | | OPENONG SIZE SHUTTER SIZE, SHUTTER SPAN | | | HOR. OR VER., STORM BARS REQUIRED, | | | ANCHOR SPACING, TYPE ANCHOR, IF STORM | | | PANELS REQUIRE BOLTS. | | | | | | 3)- DISCREPANCY SHEET A-3 RPPF PLAN | | | DEPICTS A CONVENTIALLY FRAMED ROOF VS. | | | STRUC. PLANS INDICATING A TRUSS PLAN. | | | | | | 4)- FL ENERGY CODE 400. ENERGY CALS. | | | | | | 5)-SBC 803.3 MINIMUM INTERIOR FINISH | | | SCHEDULE. | | | | | | 6)- FL ACC CODE 1997 REQUIREMENTS FOR | | | TOLIET ROOMS PER 4.22. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|