Plan Review Notes
Plan Review Notes For Permit 01051184
Permit Number 01051184
Review Stop P
Sequence Number 1
Notes
Date Text
2001-05-24 00:00:00REVIEW NOTES:...PASSED....
  
 ...PROVISO...
  
 1) TUB IN BATH 3 WILL REQUIRE 2" PIPE
 AND A VENT 8' MAX FROM TRAP PER SPC-94
 TABLE 908.1.
  
 2) LAV IN BATH 2 WILL REQUIRE 2" PIPE
 OR A VENT WITHIN 5' MAX FROM LAV FOR
 1-1/2" PIPE. SPC-94 TABLE 908.1.
  
 3) W/C MOVED IN BATH 4 WILL REQUIRE A
 TEST WITH 5' OF HEAD PRESSURE AT 2ND
 ROUGH. SPC-94 SEC. 311.2
  
 4) ALL NEW SHOWERS WILL REQUIRE TESTS
 AND MANUFACTURED CORNERS AT CURBS.
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377