| Notes |
| Date |
Text |
| 2001-05-24 00:00:00 | REVIEW NOTES:...PASSED.... | | | | | | ...PROVISO... | | | | | | 1) TUB IN BATH 3 WILL REQUIRE 2" PIPE | | | AND A VENT 8' MAX FROM TRAP PER SPC-94 | | | TABLE 908.1. | | | | | | 2) LAV IN BATH 2 WILL REQUIRE 2" PIPE | | | OR A VENT WITHIN 5' MAX FROM LAV FOR | | | 1-1/2" PIPE. SPC-94 TABLE 908.1. | | | | | | 3) W/C MOVED IN BATH 4 WILL REQUIRE A | | | TEST WITH 5' OF HEAD PRESSURE AT 2ND | | | ROUGH. SPC-94 SEC. 311.2 | | | | | | 4) ALL NEW SHOWERS WILL REQUIRE TESTS | | | AND MANUFACTURED CORNERS AT CURBS. | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8377 |
|