| Plan Review Notes For Permit 01051150 |
| Permit Number |
01051150 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-01 00:00:00 | REVIEW NOTES: FAILED | | | | | | REFERENCE SGC-97 - TABLE 305.4A - | | | TABLE 305.4E - TRACPIPE - TABLE N-4 | | | | | | DISTANCE TO MOST REMOTE OUTLET PER | | | NUMBERS SUPPLIED 91' SO 100' ON TABLES | | | WAS DISTANCE USED. | | | | | | TOTAL FIXTURE UNITS USED WAS 632K | | | | | | USING THIS INFORMATION THE SIZING OF | | | PIPE SUBMITTED IS NOT LARGE ENOUGH. | | | 2" TO FIRST TEE, 1-1/2"X1'X2". | | | P.E. PIPE TO BE 1-1/2" TO POOL HEATER | | | 1'X1/2"X3/4" GALV. TEE | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|