Plan Review Notes
Plan Review Notes For Permit 01051150
Permit Number 01051150
Review Stop P
Sequence Number 1
Notes
Date Text
2001-06-01 00:00:00REVIEW NOTES: FAILED
  
 REFERENCE SGC-97 - TABLE 305.4A -
 TABLE 305.4E - TRACPIPE - TABLE N-4
  
 DISTANCE TO MOST REMOTE OUTLET PER
 NUMBERS SUPPLIED 91' SO 100' ON TABLES
 WAS DISTANCE USED.
  
 TOTAL FIXTURE UNITS USED WAS 632K
  
 USING THIS INFORMATION THE SIZING OF
 PIPE SUBMITTED IS NOT LARGE ENOUGH.
 2" TO FIRST TEE, 1-1/2"X1'X2".
 P.E. PIPE TO BE 1-1/2" TO POOL HEATER
 1'X1/2"X3/4" GALV. TEE
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377