2001-06-12 00:00:00*******************PROVISO**************
  
 CALL FOR AN INSPECTION PRIOR TO CONCEALI
 NG DUCTS OR WELDS WITH PAINT OR ANY OTHE
 R MATERIAL.IF DUCT IS TO BE WRAPPED WI
 TH A TWO LAYERED FIRE WRAP, CALL FOR AN
 INSPECTION ON THE FIRST LAYER BEFORE THE
 SECOND LAYER IS APPLIED.
  
 NOTE:MINIMUM SLOPE FOR GREASE HOOD
 DUCT SYSTEMS IS 1 INCH PER FOOT
 (1997 SMC 505.4), NOT 1/4 PER
 FOOT AS DICTATED IN NFPA 96.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.