| Plan Review Notes For Permit 01051077 |
| Permit Number |
01051077 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-01 00:00:00 | DENIED | | | PROVIDE INFORMATION ON DUCTS BOTH | | | EXHAUST AND MAKE UP AIR | | | IF MAKE UP AIR ENTERS HOOD UNDER MAIN | | | BODY OF HOOD A FIRE DAMPER WILL BE | | | REQUIRED PER NFPA 96. PROVIDE CLEAR | | | ENOUGH DRAWING TO INDICATE ANY | | | MATERIAL/PHYSICAL SEPARATION BETWEEN | | | HOOD AND MAKE UP AIR PLENUM TO INDICATE | | | FIRE DAMPER REQUIREMENT |
|