| Notes |
| Date |
Text |
| 2001-06-01 00:00:00 | 1) NO DRAWINGS OF THE EXHAUST DUCT WHEN | | | IT LEAVES THE TOP OF THE HOOD. PLEASE | | | PROVIDE DUCT DRAWING. | | | 2) A FIRE DAMPER IS REQUIRED AT SUPPLY | | | AIR OPENING IF IT IS PRESENT UNDER THE | | | WELDED PORTION OF THE HOOD. | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SUPPRESSION SYSTEM. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|