| Plan Review Notes For Permit 01051070 |
| Permit Number |
01051070 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-04 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLANS SHOW AIC RATING FOR PANELS BUT NOT | | | FOR MAINS. | | | | | | 2) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | FAMILY ROOM | | | | | | 3) PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | | MECHANICAL CODE. | | | ALSO IN ATTIC FOR AHU`S | | | | | | 4) PLEASE NOTE MISSING OUTLET(S) REQ`D | | | BY 210-52E OF THE NEC. | | | | | | 5)NOTE: PLEASE NOTE OUTLET SPACING FOR | | | KITCHEN PENINSULAR PER 210-52-C-3 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|