| Plan Review Notes For Permit 01051022 |
| Permit Number |
01051022 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-06-21 00:00:00 | 1) GENERATOR ROOM IS TO BE AT LEAST | | | TWO HOUR FIRE RATED AND BE EQUIPPED | | | WITH B LABELED (1 1/2 ) RATED FIRE | | | DOORS. | | | 2) FIRE DAMPERS REQUIRED FOR ANY | | | VENTILATION LOUVERS. | | | 3) VENTING OF FUEL TANK TO COMPLY WITH | | | APPLICABLE STANDARDS AND BE VISIBLE. | | | 4) PLEASE PROVIDE WELDING CERTIFICATIONS | | | TO MECHANICAL DIVISION. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|