2001-06-21 00:00:001) GENERATOR ROOM IS TO BE AT LEAST
 TWO HOUR FIRE RATED AND BE EQUIPPED
 WITH B LABELED (1 1/2 ) RATED FIRE
 DOORS.
 2) FIRE DAMPERS REQUIRED FOR ANY
 VENTILATION LOUVERS.
 3) VENTING OF FUEL TANK TO COMPLY WITH
 APPLICABLE STANDARDS AND BE VISIBLE.
 4) PLEASE PROVIDE WELDING CERTIFICATIONS
 TO MECHANICAL DIVISION.
  