| Plan Review Notes For Permit 01051013 |
| Permit Number |
01051013 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-14 00:00:00 | GAS PERMIT; | | | | | | 1.GAS PERMIT REQUIRED. | | | | | | 2.PROVIDE SECOND STAG REGULATOR SPEC- | | | IFICATIONS FOR REVIEW. | | | | | | 3.PROVIDE COPIES OF GAS SIZING CHARTS | | | USED TO SIZE PIPE. | | | | | | 4.PIPING AFTER SECOND STAG REGULATOR, | | | LENGTH IS NOT ACCURATELY SHOWN.(MORE | | | THAN TEN FEET OF 1 1/4 PIPE) | | | | | | GAS PLAN REVIEW BY ; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|