| Plan Review Notes For Permit 01051006 |
| Permit Number |
01051006 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-02 00:00:00 | PLUMBING PLAN REVIEWDENIED | | | (1) SHT A-1 MINIMUM FACILITIES REQ. | | | SPC-94 SEC 407.2.2,TAB 407,MEN'S & | | | WOMEN'S REST RM'S, ONE OF EACH DIRECTLY | | | ACCESSIBLE TO THE PUBLIC,FROM THE AREA | | | THEY ARE INTENDED TO SERVE, TO COMPLY | | | W/FACBC 97 SEC 4.16 | | | LOCATION OF PLUMBING FIXTURES SEC 404.2. | | | TOILET RM'S SHALL NOT OPEN DIRECTLY INTO | | | RM'S USED FOR THE PREPRATION OF FOOD | | | FOR SERVICE TO THE PUBLIC. | | | (2) GREASE TRAP MIN SIZE 750 GALS, FAC | | | 10D-6.054(3)(D) & WPB RSTP ORD #2938-96 | | | GREASE INTERCEPTORS SHALL NOT BE LOCATED | | | WITHIN FOOD STORAGE,PREPRATION, OR CLEAN | | | EQUIPMENT STORAGE AREAS AND SHALL BE | | | READLY ACCESSIBLE, FOR MAINTENANCE. | | | (3) SHT P-1 PLBG NOTES #1 CURRENT CODE. | | | STD PLBG.CODE 94, | | | NOTE # 13 AIR CHAMBERS TO BE ACCESSIBLE | | | & RECHARGEABLE SPC 94 SEC 607.8.3 | | | (4) SHT P-1 WATER SUPPLY, PROTECTED WITH | | | A RPZV BACK FLOW PREVENTER SEC 606. | | | END OF COMMENTS PAUL SCHMITZ | | | QUESTIONS 561-659-8096 X 8233 |
|