| 2001-06-11 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01051002 |
| | 222 LAKEVIEW SUITE # 1600 |
| | CATALFUMO CONT. |
| | P 694-3000 |
| | |
| | 1)- TITLE SHEET CODE COMPLIANCE & EGRESS |
| | NOTES: FINISH MATERIALS COMPLY WITH |
| | FLAME SPREAD RATING AS REQUIRED BYTHE |
| | STANDARD BUILDING CODE, 1997 EDITION. |
| | |
| | 2)- NOTE # 1 REFERS BACK TO SBC CHAPTER |
| | 23 FOR MINIMUM ALLOWANCE 5 LBS./ SQ FT |
| | LATERAL LOAD REQUIREMENTS, THERE IS NO |
| | 2305.9 AS STATED ON PLANS. |
| | |
| | 3)- HANDICAPPED BARRIERS PER PLAN |
| | SBC SECTION 4.1.6/4.1.9 SHOULD READ 1997 |
| | FLORIDA ACCESSIBILITY CODE FOR BUILDING |
| | CONSTRUCTION. |
| | |
| | 4)- SHEET 01 LEGEND: PARTITION TYPE 1 |
| | LIST UL LISTING OR GYPSUM ASSOC # FOR |
| | ASSEMBLY ALSO INDICATE STANDARD BUILDING |
| | CODE 704.2 INTERIOR WALLS & PARTITION |
| | FIRE SEPERATION REQUIREMENTS. |
| | |
| | 5)- SBC 704.2.1.4 CORRIDOR PARTITIONS |
| | SHALL BE EFFECTIVELY & PERMANETLY WITH |
| | SIGN OR STENCILING IN A MANNER ABOVE ANY |
| | DECORATIVE CEILING OR CONSEALED SPACE |
| | "FIRE & SMOKE BARRIER PROTECT ALL OPEN-I |
| | NGS". |
| | |
| | 6)- SBC 609.2.1. TYPE I & TYPE II BUILD- |
| | INGS REQUIRE ALL WOOD IN PARTITIONS, |
| | FIRE TREATED WOOD. |
| | |
| | 7)- SHEET 49.01. MISSING IS THE MINIMUM |
| | INTERIOR FINISH CLASSIFICATION SCHEDULE |
| | SBC TABLE 803.3. |
| | |
| | 8)- SBC 412.9 MANUAL FIRE ALARM BOXES |
| | SHALL BE PROVIDED. |
| | |
| | 9)- FIRE SPRINKLERS SBC 412.10 HI-RISE |
| | TYPE BUILDINGS REQUIRE FIRE SPRINKLERS. |
| | |