| Plan Review Notes For Permit 01050998 |
| Permit Number |
01050998 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-11 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE CALRIFY EQUIPMENT AND | | | OCP AT DETACHED BLDG? PANEL SCHEDULE | | | SHOWS 100A MAIN AND RISER SHOWS 75A | | | MAINALSO SHOWS 1/0 WIRE FOR 150A FEED? | | | | | | | | | 2)NOTE: PLEASE NOTE THAT LOADS SHOWN | | | FOR EXISTING 200A MAIN AND NEW LOAD | | | BEING ADDED EXCEEDS RATING OF MAIN. | | | PLEASE NOTE THAT LOAD ADDS UP TO 203.2 | | | AMPS. | | | ALSO PLEASE NOTE THAT MAIN PANEL | | | SCHEDULE DOES NOT LIST ANY BRKR FEEDING | | | DETACHED BLDG.? | | | | | | 3)NOTE: PLEASE CLARIFY APPLIANCE CIRCUIT | | | BEING SHOWN AT 15A FOR DETEACHED BLDG. | | | | | | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 5)NOTE: PLEASE CLARIFY IF BOTH MAINS | | | AT DETACHED BLDG IS BEING INSTALLED. | | | PLANS SHOW MCB AND DISCONNECT ON THE OUT | | | SIDE OF STRUCTURE? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|