| Plan Review Notes For Permit 01050966 |
| Permit Number |
01050966 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-07 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01050966 | | | 1 N. CLEMATIS SUITE 5TH FLOOR | | | | | | 1)- A SUITE # WILL BE REQUIRED TO | | | COMPLETE THE ADDRESS. | | | | | | 2)- FL ACCESSIBILITY CODE: OFFICE #4 | | | SHEET A2-E REQUIRES 18" CLEARENCE PER | | | FL ACC CODE 4.13.6. | | | | | | 3)- SHEET A6-E DETAIL #7 PER U-465 UL | | | LISTING, STUD SPACING NOT GIVEN. | | | | | | 4)- SHEET A6-E DEAIL #7 CORRIDOR PARTI- | | | TIONS & FIRE RATED WALLS REQUIRED TO | | | HAVE PROTECTED OPENINGS SHALL PERMANETLY | | | IDENTIFY WITH SIGNS OR STECLING "FIRE & | | | SMOKE BARRIER PROTECT ALL OPENINGS". | | | | | | 5)- SBC 704.2.1.2. DETAILS 6& 7 OF A6-E | | | ALL PARTITIONS REQUIRED TO HAVE FIRE RES | | | ISTANCE RATING SHALL EXTEND FROM THE TOP | | | OF THE FLOOR BELOW TO THE CEILING ABOVE | | | AND SHALL BE SECURELY ATTACHED & SEALED, | | | HAVING A FIRE RESISTANCE RATING AT LEAST | | | EQUAL FOR THE PARTITION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|