| Plan Review Notes For Permit 01050945 |
| Permit Number |
01050945 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-19 00:00:00 | REVIEW NOTES...FAILED.. | | | | | | 1) CHART FOR CSST PIPE NOT ACCEPTABLE. | | | CHART 305.4F OF SGC-97 MUST BE USED. AND | | | 80' OF 1" CSST ONLY ALLOWS FOR 132,000 | | | BTU'S. | | | | | | 2) 1/2" GALV. DROP TO RANGE TO BE SIZED | | | AT 3/4". 1/2" ONLY ALLOWS FOR 57,000 BTU | | | AT 80'. | | | | | | RESIZE AND RESUBMIT USING APPROIATE | | | CHART AND PIPE. | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8377 |
|