| Plan Review Notes For Permit 01050928 |
| Permit Number |
01050928 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-18 00:00:00 | 1) THE FIRE ALARM AND FIRE SPRINKLER | | | SYSTEMS ARE TO BE MONITORED BY A | | | LICENSED UL LISTED CENTRAL STATION | | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | | 2) FIRE ALARM SYSTEM TO BE CLASS A OR | | | FULLY ADDRESSABLE. | | | 3) SMOKE DETECTORS WHEN INSTALLED ARE TO | | | BE A MINIMUM OF THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | 4) FIRE ALARM SYSTEM WHEN ACTIVATED IS | | | TO BE AUDIBLE THROUGHOUT THE BUILDING. | | | 5) FIRE ALARM HORN STROBE DEVICES ARE TO | | | BE INSTALLED BETWEEN 80-96 INCHES FROM | | | FINISHED FLOOR. | | | 6) MANUAL PULL STATIONS SHALL BE MOUNTED | | | BETWEEN 3 1/2 TO 4 1/2 FEET FROM THE | | | FLOOR. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|