| Plan Review Notes For Permit 01050883 |
| Permit Number |
01050883 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-07-18 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT ANY | | | HANDWRITTENCHANGES ON PLANS ARE TO BE | | | SIGNED,DATED BY ARCH OF RECORD. 481.221 | | | | | | 2)NOTE: PLEASE NOTE THAT LOAD | | | CALCULATIONS DO NOT INCLUDE ALL LOADS | | | REQ`D BY NEC ART 220. NO A/C, NO SM APPL | | | PLEASE REVISE | | | | | | 3)NOTE: PLEASE NOTE THAT UTILITY ROOM | | | OUTLET TO BE GFI PER 210-8. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELELCTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|