Plan Review Notes
Plan Review Notes For Permit 01050850
Permit Number 01050850
Review Stop P
Sequence Number 2
Notes
Date Text
2001-10-15 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SPC-94 TABLE 407 REQUIRED 2 BATHROOMS
 1 MALE AND 1 FEMALE.
  
 2) DOOR TO RESTROOM SHALL NOT OPEN INTO
 CLEAR FLOOR SPACE OF DRINKING FOUNTAIN,
 OR LAV.
  
 3) IRRIGATION ON SEPARATE PERMIT.
 PLUMBING CONTRACTOR TO INSTALL A SEPAR-
 ATE TEE WITH A VALVE AND AN N-36 WATTS
 VACUUM BREAKER TO TIE INTO.
  
 4) TWO WAY CLEAN OUTS ARE REQUIRED FOR
 EACH BLDG DRAIN WHERE IT TIES INTO THE
 BLDG SEWER.
  
 5) SHEET E-1, WATER RISER. AIR CHAMBERS
 ARE "QUICK FIX" WATER HAMMER ARRESTORS
 SHALL BE INSTALLED PER MANUFACTURE'S
 INSTALLATION AND WH-PDI 201. PLACE CLOSE
 TO SOURCE OF SHUTOFF, NOT ON TOP OF DROP
 AS SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 569 8096 EXT. 8377