| Plan Review Notes For Permit 01050850 |
| Permit Number |
01050850 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-29 00:00:00 | DENIED; | | | | | | 1.SHOW CALCULATIONS FOR EMPLOYEES TO | | | COMPLY WITH 94 SPC TABLE 407.SHOW | | | LOCATION OF DRINKING FOUNTAIN REQUIRED | | | SEE TABLE 407 MISCELLANEOUS FIXTURES. | | | 2.FLOOR DRAIN IN BATHROOM SHALL HAVE A | | | TRAP PRIMER 409.4.1.1. | | | 3.3" FLOOR DRAIN IN S.E. CORNER OF | | | BUILDING. | | | A.WILL THERE BE ANY CEMICALS OR | | | ANYTHING THAT WILL DAMAGE THE | | | DRAINAGE SYSTEM? | | | B. FLOOR DRAIN MUST BE VENTED PER. | | | TABLE 908.1. | | | C.FLOOR DRAIN SHALL BE A DEEP SEAL | | | TYPE. | | | 4.PAGE F-1. PLUMBING LINE DRAWING. FLOOR | | | DRAIN NOT VENTED PROPERLY (TOILET | | | FLUSHES PAST FLOOR DRAIN). FLOOR DRAIN | | | SHOULD COME OFF LAVITORY DRAIN LINE. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|