| Plan Review Notes For Permit 01050850 |
| Permit Number |
01050850 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-07 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT NO PANEL SCHED- | | | -ULES WERE SUBMITTED. | | | NO LOAD CALCUALTIONS WERE SUBMITTED FOR | | | REVIEW. | | | | | | 2)NOTE: PLEASE NOTE, PLANS NEED TO SHOW | | | ALL BRANCH CIRCUIT #`S ON PLANS AND | | | CORRELATE WITH SUBMITTED PANEL SCHEDULES | | | | | | 3)NOTE: PLEASE CLARIFY ANY A/C THAT MAY | | | BE INSTALLED FOR OFFICE/WAREHOUSE. | | | PLEASE NOTE ANY A/C UNITS WILL NEED TO | | | BE SHOWN ON PLANS WITH ALL DISCONNECTS | | | PER 440-11. | | | | | | 4)NOTE: PLEASE CLARIFY RISER SHOWING | | | 4-4/0`S GOING TO LIGHTING CONTACTOR??? | | | | | | 5)NOTE: PLEASE NOTE RISER DIAGRAM NEEDS | | | TO SHOW ALL WIRE/CONDUIT SIZES FROM | | | METER-MAIN-PANEL. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|